1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
/SOURCE
14WHITE         1.02       60.       0.0                           -1.
/BRANCH
  WHITE YELLOW               .05   .20 
  YELLOWGREEN                .05   .20  
  GREEN RED                  .05   .20 
  RED   BLUE                 .10   .40  
/LOAD FLOW
C              Next come power constraints of the load flow.   There will be one 
C              for each non-slack generator:
  RED                           -0.4            -.14     .85    1.15     
  GREEN                          1.0             0.3     .85    1.15
  BLUE                          -.15            .025     .85    1.15    
  YELLOW                        -0.6            -0.2     .85    1.15    
C    The following load-flow miscellaneous data card has two peculiarities.  The
C    use of  VSCALE = 1.414  is the special flag requesting RMS rather than peak
C    voltages.   The use of   KTAPER = 0   ensures constant acceleration factors
C    (this works for this data).
C         NNNOUT  NITERA  NFLOUT  NPRINT  RALCHK  CFITEV  CFITEA  VSCALE  KTAPER
               1     500      20       1  .00001     0.1     7.0   1.414       0
/REQUEST
FIX SOURCE   { An EMTP load flow will satisfy requested phasor power injections.