diff options
Diffstat (limited to 'benchmarks/dcp7.dat')
-rw-r--r-- | benchmarks/dcp7.dat | 59 |
1 files changed, 59 insertions, 0 deletions
diff --git a/benchmarks/dcp7.dat b/benchmarks/dcp7.dat new file mode 100644 index 0000000..1100d91 --- /dev/null +++ b/benchmarks/dcp7.dat @@ -0,0 +1,59 @@ +BEGIN NEW DATA CASE
+C BENCHMARK DCPR-7
+C Test of 3-phase Pi-circuit that is excited by 3 in-phase sources that are
+C present during the phasor solution. No transients (phasor continuation).
+DIAGNOSTIC 0 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+ .05 1.0 60. 60.
+ 1 1 1 1 1 -1
+ 2 -1 { Turn off the diagnostic on step number 2
+ RECA .001 { Short the receiving end through R=1.E-3
+ RECB .001 { ohm resistors, so that lots of current
+ RECC .001 { will flow (no subtle effects here!).
+ 1SENDA RECA 1.0 1.0 1.E4 { 1st card of 3-phase Pi-circuit
+ 2SENDB RECB 0.7 0.3 -2.E3 1.0 1.0 1.E4
+ 3SENDC RECC 0.7 0.3 -2.E3 0.7 0.3 -2.E3 1.0 1.0 1.E4
+BLANK card ending branch cards
+ GENA SENDA -1.0 9.0 { 1st of 3 permanently-closed switches
+ GENB SENDB -1.0 9.0
+ GENC SENDC -1.0 9.0
+BLANK card ending switch cards
+14GENA 100. 1.0 { Note all 3 sources} -1.
+14GENB 100. 1.0 { have a phase angle} -1.
+14GENC 100. 1.0 { of zero degrees.} -1.
+BLANK card ending source cards
+C Total network loss P-loss by summing injections = 6.246626371768E+03
+C Output for steady-state phasor switch currents.
+C Node-K Node-M I-real I-imag I-magn
+C GENA SENDA 0.41644176E+02 -0.45752035E+00 0.41646689E+02
+C GENB SENDB 0.41644176E+02 -0.45752035E+00 0.41646689E+02
+C GENC SENDC 0.41644176E+02 -0.45752035E+00 0.41646689E+02
+C Last inject: GENC
+C Last inject: SENDC 100. 100. 41.644175811789 41.646688990975
+C Last inject: 0.0 0.0 -.4575203468966 -0.6294501
+C Step Time RECC RECB RECA SENDC SENDB
+C
+C GENC
+C *** Phasor I(0) = 0.4164418E+02 Switch "GENA " to "SENDA " closed
+C *** Phasor I(0) = 0.4164418E+02 Switch "GENB " to "SENDB " closed
+C *** Phasor I(0) = 0.4164418E+02 Switch "GENC " to "SENDC " closed
+C 0 0.0 .0416441758 .0416441758 .0416441758 100. 100.
+C 100.
+C 1 .05 .0397499231 .0397499231 .0397499231 95.10565163 95.10565163
+C 95.10565163
+ 1
+C 20 1.0 .0416440951 .0416440951 .0416440951 100. 100.
+C 100.
+C Variable max : .0416441758 .0416441758 .0416441758 100. 100.
+C 100.
+C Times of max : 0.0 0.0 0.0 0.0 0.0
+C 0.0
+C Variable min : -.041644069 -.041644069 -.041644069 -100. -100.
+C -100.
+C Times of min : 0.5 0.5 0.5 0.5 0.5
+C 0.5
+ PRINTER PLOT { Axis limits : (-4.164, 4.164)
+ 143 .1 0.0 1.0 RECA { This receiving end voltage is nice & sinusoidal
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+BLANK
|