summaryrefslogtreecommitdiffstats
path: root/benchmarks/dcp17.dat
diff options
context:
space:
mode:
Diffstat (limited to 'benchmarks/dcp17.dat')
-rw-r--r--benchmarks/dcp17.dat124
1 files changed, 124 insertions, 0 deletions
diff --git a/benchmarks/dcp17.dat b/benchmarks/dcp17.dat
new file mode 100644
index 0000000..0e46d68
--- /dev/null
+++ b/benchmarks/dcp17.dat
@@ -0,0 +1,124 @@
+BEGIN NEW DATA CASE
+C BENCHMARK DCPR-17
+C Copied from DCNEW-2, only with critical debug printout turned on.
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+C DIAGNOSTIC 0 0 0 0 9 9 0 9 9 9 0 9 9 3 9 9 0 9 9
+ABSOLUTE U.M. DIMENSIONS, 20, 2, 50, 100
+ .000200 .070
+ 1 1 1 1 1 -1
+ 2 -1 5 5 20 20 100 100
+TACS HYBRID
+ STEP1 +BAT1 -TFAULT
+ STEP2 +BAT2 -TCLEAR
+ FIRE -STEP0 +STEP1 -STEP2
+C --------- TACS UNITY SIGNAL SOURCE
+11STEP0 1.0 -1.0
+C --------- EMTP OUTPUT TO TACS
+90BAT1
+90BAT2
+90TFAULT
+90TCLEAR
+BLANK card ends all TACS data cards
+C --------- EMTP CONNECTIVITY
+ BUSA0 1.0E+8
+ BUSB0 1.0E+8
+ BUSC0 1.0E+8
+ BUSA5 BUSA1 0.001 1
+ BUSB5 BUSB1 0.001 1
+ BUSC5 BUSC1 0.001 1
+C --------- TRANSMISSION LINES (0.001 OHMS AND 1.0 MILLI HENRY)
+ BUSA1 BUSA0 1.0E-2 1.0 1
+ BUSB1 BUSB0 BUSA1 BUSA0 1
+ BUSC1 BUSC0 BUSA1 BUSA0 1
+C --------- RESISTANCES FROM BUS1 TO SWITCH (BUS2 TO GROUND)
+ BUSA1 BUSA2 0.0001 1
+ BUSB1 BUSB2 0.0001
+ BUSC1 BUSC2 0.0001
+C --------- EMTP CONNECTIVITY REQUIREMENT
+ BUSFS 1.0E+6
+ BUSFS BUSF0 1.0E-5
+C --------- RESISTANCES IN PARALLEL TO SWITCHES (BUS2 TO GROUND)
+ BUSA2 1.0E+9
+ BUSB2 1.0E+9
+ BUSC2 1.0E+9
+C --------- CIRCUIT FOR SWITCH CONTROL
+ BAT1 1.0
+ BAT2 1.0
+ BAT1 TFAULT 1.0
+ BAT2 TCLEAR 1.0
+C --------- MECH NETWORK
+ BUSMSM 1.E+09 1
+ BUSMS BUSMSM 1.0E-3 1
+BLANK card bounds the last branch card
+C --------- TIME OF FAULT AND TIME OF CLEARING
+ TFAULT .05001 { Fault is applied 1/2 DELTAT after 50 msec
+ TCLEAR 3600.0
+C --------- TACS CONTROLLED SWITCHES
+11BUSA2 FIRE
+11BUSB2 FIRE
+11BUSC2 FIRE
+ BUSA9 BUSA5 -1.0 1.0 1
+ BUSB9 BUSB5 -1.0 1.0 1
+ BUSC9 BUSC5 -1.0 1.0 1
+BLANK card ends the last electric network switch card
+C --------- EXCITATION SOURCE VOLTAGE (ACTUAL VALUE SET BY SS)
+14BUSFS 0.001 0.00001 -1.0
+C --------- INFINITE BUS SOURCE VOLTAGES
+14BUSA0 3000.0 60.0 0.0 -1.0
+14BUSB0 3000.0 60.0 -120.0 -1.0
+14BUSC0 3000.0 60.0 +120.0 -1.0
+C --------- BATTERIES FOR SWITCH CONTROL
+14BAT1 2.0 0.00001 -1.0
+14BAT2 3.0 0.00001 -1.0
+C --------- MECH INPUT TORQUE (ACTUAL VALUE SET BY SS) :
+14BUSMS -1 0.0000001 0.00001 -1.0
+C --------- SYNCHRONOUS MACHINE SPECIFICATIONS
+C --------- UM DATA
+19 UM
+ 1
+BLANK CARD ENDING CLASS 1 UM DATA
+C --------- UM-1 MACH-TABLE
+ 1 2 1111BUSMSM 1 0.0373
+ 0.0057815
+ 0.0055850
+3030.0 15.0 BUSFS BUSMS
+C --------- UM-1 COIL-TABLE
+ BUSA9 1
+0.001542 0.0005595 BUSB9 1
+0.001542 0.0005595 BUSC9 1
+0.0010 0.0003767 BUSF0 1
+0.01834 0.0002075 1
+0.07560 0.0001335 1
+BLANK card ends all U.M. data cards
+BLANK card ending all electric network sources
+C --------- REQUEST FOR NODE VOLTAGE OUTPUT
+ BUSA1 BUSA0 BUSMSM
+C Step Time BUSA1 BUSA0 BUSMSM BUSA9 BUSB9
+C BUSA5 BUSB5
+C
+C BUSC5 BUSA1 BUSB1 BUSC1 BUSA1
+C BUSC1 BUSA0 BUSB0 BUSC0 BUSA2
+C
+C UM-1 UM-1 UM-1 UM-1 UM-1
+C OMEGM THETAM IPA IPB IPC
+C *** Phasor I(0) = 0.2072773E+04 Switch "BUSA9 " to "BUSA5 " closed
+C *** Phasor I(0) = -0.8157515E+03 Switch "BUSB9 " to "BUSB5 " closed
+C *** Phasor I(0) = -0.1257021E+04 Switch "BUSC9 " to "BUSC5 " closed
+C 0 0.0 2924.682776 3000. 376.9911184 2072.772625 -815.751494
+C -1257.02113 2072.772622 -815.751493 -1257.02113 .2924025E-5
+C 376.9911184 1.174129749 2072.761251 -815.747018 -1257.01423
+C 1 .2E-3 2857.300587 2991.476701 376.9911184 2047.702816 -668.685067
+C -1379.01775 2047.702813 -668.685066 -1379.01775 .2837623E-5
+C 376.9911184 1.174129749 2047.702816 -668.685067 -1379.01775
+BLANK card ending selective variable output request (node voltages, here)
+C 350 .07 .7035049802 927.0509831 376.7447835 2436.93984 10869.29497
+C Last step: -13306.2348 -4598.10996 -807.56516 5405.675122 7035.049802
+C Last step: 376.774892 1.169600292 2436.93984 10869.29497 -13306.2348
+ PRINTER PLOT
+ 194 8. 0.0 96. UM-1 TQGEN { Plot limits: (-0.913, 1.467)
+ CALCOMP PLOT
+ 194 9. 0.0 90. UM-1 IPA
+BLANK card ending batch-mode plot cards
+BEGIN NEW DATA CASE
+BLANK
+