summaryrefslogtreecommitdiffstats
path: root/benchmarks/dcp1.dat
diff options
context:
space:
mode:
Diffstat (limited to 'benchmarks/dcp1.dat')
-rw-r--r--benchmarks/dcp1.dat70
1 files changed, 70 insertions, 0 deletions
diff --git a/benchmarks/dcp1.dat b/benchmarks/dcp1.dat
new file mode 100644
index 0000000..39b1034
--- /dev/null
+++ b/benchmarks/dcp1.dat
@@ -0,0 +1,70 @@
+BEGIN NEW DATA CASE
+C BENCHMARK DCPR-1
+C Test of 1-phase constant-parameter line. One switch is permanently
+C closed. No transients. Plot of receiving end voltage is sinusoid.
+DIAGNOSTIC 0 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+ .000100 .020 60. 60.
+ 1 1 1 1 1 -1
+ 2 -1 5 5 20 20
+ REC .001 { Near short at receiving end to ground } 3
+-1SEND REC 0.3 0.4 12.6 100. { 1-phase distributed line
+BLANK card ending branch cards
+ GEN SEND -1.0 1.0 { Permanently closed switch at sending end
+BLANK card ending switch cards
+14GEN 100. 60. { 60-Hz phasor solution } -1.
+BLANK card ending source cards
+C Total network loss P-loss by summing injections = 5.992836086590E+01
+C GEN
+C SEND 100. 100. 1.1985672173179 1.9672525544427
+C 0.0 0.0 -1.559974114699 -52.4640241
+C Step Time REC REC SEND GEN REC
+C TERRA TERRA
+C 0 0.0 .001198266 .001198266 100. 100. 1.198266
+C 1 .1E-3 .0012585558 .0012585558 99.92894726 99.92894726 1.258555833
+ 1
+C 200 .02 .0019138946 .0019138946 30.90169944 30.90169944 1.913894577
+C Variable max : .0020173699 .0020173699 100. 100. 2.017369917
+C Times of max : .0025 .0025 0.0 0.0 .0025
+C Variable min : -.002017453 -.002017453 -99.9921044 -99.9921044 -2.01745286
+C Times of min : .0108 .0108 .0083 .0083 .0108
+ PRINTER PLOT
+ 194 4. 0.0 20. REC { Axis limits : (-2.017, 2.017)
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 2nd subcase involves use of trapped-charge source to initialize
+C an initially-disconnected single-phase line. Later, energize the
+C line by switch closure at 3 msec. The data was supplied by Dipl.
+C Ing. Bernd Stein of FGH (Mannheim, Germany) during April of 1986.
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+DIAGNOSTIC 0 9 0 9 9 9 0 9 9 9 0 9 9 9 9 9 9 9 9
+ALTERNATE DIAGNOSTIC PRINTOUT, 0, 0, 0, 0, { Need for 2nd or later subcase only
+ .000100 .020 { Unlike 1st of 2 subcases, here XOPT = COPT = 0
+ 1 1 0 1 1 -1
+ 2 -1 5 5 20 20 { Switch to alternate on step 2
+ GEN SWITCH 39.8
+ SWITCH 1000.
+-1SEND REC .3055 5.819 .0121 138.
+BLANK card ending branch cards
+ SEND SWITCH .003 1.0 { Transient begins at 3 msec with closure
+BLANK card ending switch cards
+C 1 2 3 4 5 6 7 8
+C 78901234567890123456789012345678901234567890123456789012345678901234567890
+14GEN 100. 60. -1.0
+14SEND -1 -100. .001 { Trapped-charge source } 5432.
+C End multiple-frequency phasor solution data. The first source is a regular
+C 60-Hertz generator, whereas the second has f = 1/1000 Hz for trapped charge
+BLANK card ending source cards
+C Total network loss P-loss by summing injections = 4.998874616296E+00
+C Last gen: SEND -100. 100. -.17408297E-12 .10491662826E-5 .8704148513E-11
+C Last gen: 0.0 180.0 -.1049166283E-5 -90.0000095 -.5245831413E-4
+C Step Time REC SEND SWITCH GEN
+C 0 0.0 -100. -100. 99.97749233 100.
+C 1 .1E-3 -100. -100. 99.96299489 99.92894726
+C 2 .2E-3 -100. -100. 99.80645119 99.71589003
+ 1 { Request for the output of all four node voltages
+C 200 .02 138.2909745 45.09406184 45.09406184 30.90169944
+ 144 2. 0.0 20. SEND REC { Axis limits : (-2.510, 2.052)
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+BLANK