+BEGIN NEW DATA CASE
+C 1st of 3 subcases is added 18 October 2001. It is unrelated to following
+C 2nd. Since a DO KNT loop is involved, data must be in 1st subcase.
+C 1st of 2 subcases illustrates "simultaneous usage of $PARAMETER
+C blocks and DO loops, which are used to serialize power network
+C branches." This is the way Prof. Juan Martinez of UPC in Barcelona,
+C Spain, described his latest observation of inadequacy of the new ATP
+C tools, in an E-mail message dated 16 October 2001. The attached small
+C example NEWDIS2.DAT served as the model for the present addition.
+C Among other changes, /-card data sorting was removed for simplicity.
+C It had nothing to do with the program error, which was corrected the
+C following day. Before correction, execution died early in branch input.
+$PARAMETER
+AAAAAAAA='$ENABLE '
+BBBBBBBB='$DISABLE'
+BLANK card ends block of parameter definitions
+ .000100 .010 { dT and T-max will result in 100 steps (Martinez had 400)
+ 20 -1 { Minimal printout and no plotting demonstrate simulation
+DO KNT=1, 5 /OUTPUT
+$PARAMETER
+BU1___ = KNT - 1. SERIALIZE 'BUS000'
+BU2___ = KNT SERIALIZE 'BUS000'
+BLANK card ending symbols definitions
+ BU1___BU2___ 0.075 0.5570
+ BU2___ 1000. 2387.3
+ENDDO KNT
+C The following 3 data cards will be ignored since BBBBBBBB will be replaced
+C by $DISABLE (see the first $PARAMETER block). Yet, these 3 lines
+C produce substantial output in the .LIS file because the $DISABLE is
+C dynamic. Each line of the disk file must be read since ATP has no way of
+C knowing that one of them does not end the discarding.
+BBBBBBBB
+$INCLUDE dofile.dat
+$ENABLE
+BLANK card ending BRANCH cards
+ SOURCEBUS000 MEASURING 1
+C The following data card will be ignored since AAAAAAAA will be
+C replaced by $ENABLE by the first $PARAMETER block:
+AAAAAAAA
+BLANK card ending SWITCH cards
+14SOURCE 20412.4 50.0 0.0 -1.0
+BLANK card ending SOURCE cards
+ BUS000BUS001BUS004BUS005
+C First 4 output variables are electric-network voltage differences (upper voltage minus lower voltage);
+C Next 1 output variables are branch currents (flowing from the upper node to the lower node);
+C Step Time BUS000 BUS001 BUS004 BUS005 SOURCE
+C BUS000
+C *** Phasor I(0) = 6.5184598E+01 Switch "SOURCE" to "BUS000" closed in the steady-state.
+C 0 0.0 20412.4 20398.9415 20374.7213 20372.0305 65.1845978
+C 20 .002 16513.9785 16507.6359 16496.2181 16494.9494 81.5202569
+C 40 .004 6307.7785 6310.97466 6316.72113 6317.3591 66.7198316
+C 60 .006 -6307.7785 -6296.2642 -6275.5483 -6273.2473 26.4355142
+C 80 .008 -16513.978 -16498.544 -16470.771 -16467.686 -23.945918
+C 100 .01 -20412.4 -20398.941 -20374.72 -20372.029 -65.18067
+BLANK card ending OUTPUT cards
+BLANK card ending PLOT cards
+BEGIN NEW DATA CASE
+C BENCHMARK DCNEW-2
+C 2nd of 2 subcases was the 1st prior to 18 October 2001.
+C Test of automatic U.M. initialization using 3-phase synchronous mode of
+C operation. The steady-state lasts 50 msec until a TACS "fault" occurs.
+C The machine data comes from the text by Fouad and Anderson (real units)
+C Note: WSM and Yin change comment cards in Leuven, October 22, 1990,
+C following modifications of code that change answers in 3rd or 4th
+C decimal place (peak values of PRINTER PLOTs are barely affected).
+C In response to a request for specifics, G. Papagiannis of Aristotle
+C University of Thessaloniki in Greece posted the following on February
+C 18, 1998 (public E-mail from Fargo): A. A. Fouad and P. M. Anderson;
+C "Power System Control and Stability," Iowa State University Press in
+C Ames, Iowa, USA, 1982. "An excellent treatment of synhronous machine
+C modelling" was the recommendation. Neil Fitzgerald of Electrowatt
+C Engineering (UK) Ltd concurred later that same day, adding that the
+C book "was reprinted in 1993 by the IEEE Press and I think it costs
+C around $39.00 from the IEEE." He agreed on the recommendation. As
+C for the "P. M.", this is Dr. Paul M. of PMA (Power Math Associates)
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+ABSOLUTE U.M. DIMENSIONS, 20, 2, 50, 100
+POWER FREQUENCY, 60, { Corrects possible 50-Hz declaration of European STARTUP
+ .000200 .070
+ 1 1 1 1 1 -1
+ 5 5 20 20 100 100
+TACS HYBRID
+ STEP1 +BAT1 -TFAULT
+ STEP2 +BAT2 -TCLEAR
+ FIRE -STEP0 +STEP1 -STEP2
+C --------- TACS UNITY SIGNAL SOURCE
+11STEP0 1.0 -1.0
+C --------- EMTP OUTPUT TO TACS
+90BAT1
+90BAT2
+90TFAULT
+90TCLEAR
+BLANK card ends all TACS data cards
+C --------- EMTP CONNECTIVITY
+ BUSA0 1.0E+8
+ BUSB0 1.0E+8
+ BUSC0 1.0E+8
+ BUSA5 BUSA1 0.001 1
+ BUSB5 BUSB1 0.001 1
+ BUSC5 BUSC1 0.001 1
+C --------- TRANSMISSION LINES (0.001 OHMS AND 1.0 MILLI HENRY)
+ BUSA1 BUSA0 1.0E-2 1.0 1
+ BUSB1 BUSB0 BUSA1 BUSA0 1
+ BUSC1 BUSC0 BUSA1 BUSA0 1
+C --------- RESISTANCES FROM BUS1 TO SWITCH (BUS2 TO GROUND)
+ BUSA1 BUSA2 0.0001 1
+ BUSB1 BUSB2 0.0001
+ BUSC1 BUSC2 0.0001
+C --------- EMTP CONNECTIVITY REQUIREMENT
+ BUSFS 1.0E+6
+ BUSFS BUSF0 1.0E-5
+C --------- RESISTANCES IN PARALLEL TO SWITCHES (BUS2 TO GROUND)
+ BUSA2 1.0E+9
+ BUSB2 1.0E+9
+ BUSC2 1.0E+9
+C --------- CIRCUIT FOR SWITCH CONTROL
+ BAT1 1.0
+ BAT2 1.0
+ BAT1 TFAULT 1.0
+ BAT2 TCLEAR 1.0
+C --------- MECH NETWORK
+ BUSMSM 1.E+09 1
+ BUSMS BUSMSM 1.0E-3 1
+BLANK card bounds the last branch card
+C --------- TIME OF FAULT AND TIME OF CLEARING
+ TFAULT .05001 { Fault is applied 1/2 DELTAT after 50 msec
+ TCLEAR 3600.0
+C --------- TACS CONTROLLED SWITCHES
+11BUSA2 FIRE
+11BUSB2 FIRE
+11BUSC2 FIRE
+ BUSA9 BUSA5 -1.0 1.0 1
+ BUSB9 BUSB5 -1.0 1.0 1
+ BUSC9 BUSC5 -1.0 1.0 1
+BLANK card ends the last electric network switch card
+C --------- EXCITATION SOURCE VOLTAGE (ACTUAL VALUE SET BY SS)
+14BUSFS 0.001 0.00001 -1.0
+C --------- INFINITE BUS SOURCE VOLTAGES
+14BUSA0 3000.0 60.0 0.0 -1.0
+14BUSB0 3000.0 60.0 -120.0 -1.0
+14BUSC0 3000.0 60.0 +120.0 -1.0
+C --------- BATTERIES FOR SWITCH CONTROL
+14BAT1 2.0 0.00001 -1.0
+14BAT2 3.0 0.00001 -1.0
+C --------- MECH INPUT TORQUE (ACTUAL VALUE SET BY SS) :
+14BUSMS -1 0.0000001 0.00001 -1.0
+C --------- SYNCHRONOUS MACHINE SPECIFICATIONS
+C --------- UM DATA
+19 UM
+ 1
+BLANK CARD ENDING CLASS 1 UM DATA
+C --------- UM-1 MACH-TABLE
+ 1 2 1111BUSMSM 1 0.0373
+ 0.0057815
+ 0.0055850
+3030.0 15.0 BUSFS BUSMS
+C --------- UM-1 COIL-TABLE
+ BUSA9 1
+0.001542 0.0005595 BUSB9 1
+0.001542 0.0005595 BUSC9 1
+0.0010 0.0003767 BUSF0 1
+0.01834 0.0002075 1
+0.07560 0.0001335 1
+BLANK card ends all U.M. data cards
+C --------------+------------------------------
+C From bus name | Names of all adjacent busses.
+C --------------+------------------------------
+C BUSA0 |TERRA *BUSA1 *
+C BUSB0 |TERRA *BUSB1 *
+C BUSC0 |TERRA *BUSC1 *
+C BUSA5 |BUSA1 *BUSA9 *
+C BUSA1 |BUSA0 *BUSA5 *BUSA2 *
+C BUSB5 |BUSB1 *BUSB9 *
+C BUSB1 |BUSB0 *BUSB5 *BUSB2 *
+C BUSC5 |BUSC1 *BUSC9 *
+C BUSC1 |BUSC0 *BUSC5 *BUSC2 *
+C BUSA2 |TERRA *TERRA *BUSA1 *
+C BUSB2 |TERRA *TERRA *BUSB1 *
+C BUSC2 |TERRA *TERRA *BUSC1 *
+C BUSFS |TERRA *BUSF0 *
+C BUSF0 |BUSFS *
+C < < Etc. (many more not shown) > >
+BLANK card ending all electric network sources
+C Total network loss P-loss by summing injections = 7.248075223468E+04
+C Total network loss P-loss by summing injections = 1.461915999075E+15
+C Total network loss P-loss by summing injections = 1.461915980400E+15
+C Total network loss P-loss by summing injections = 1.461915980711E+15
+C Gen 1: BUSMSM 376.99111843078 376.99111843078 -24959.40530999 24959.416549762
+C Gen 1: 0.0 0.0 23.687050562614 179.9456250
+ BUSA1 BUSA0 BUSMSM
+C Step Time BUSA1 BUSA0 BUSMSM BUSA9 BUSB9
+C BUSA5 BUSB5
+C
+C BUSC5 BUSA1 BUSB1 BUSC1 BUSA1
+C BUSC1 BUSA0 BUSB0 BUSC0 BUSA2
+C
+C UM-1 UM-1 UM-1 UM-1 UM-1
+C OMEGM THETAM IPA IPB IPC
+C *** Phasor I(0) = 2.0727726E+03 Switch "BUSA9 " to "BUSA5 " closed
+C *** Phasor I(0) = -8.1575149E+02 Switch "BUSB9 " to "BUSB5 " closed
+C *** Phasor I(0) = -1.2570211E+03 Switch "BUSC9 " to "BUSC5 " closed
+C 0 0.0 2924.682776 3000. 376.9911184 2072.772625 -815.751494
+C -1257.02113 2072.772622 -815.751493 -1257.02113 .2928573E-5
+C 376.9911184 1.174129748 2072.761251 -815.747018 -1257.01423
+C 1 .2E-3 2857.218771 2991.476701 376.9911184 2047.694642 -668.660479
+C -1379.03416 2047.69464 -668.660478 -1379.03416 .2833076E-5
+C 376.9911184 1.174129748 2047.694642 -668.660479 -1379.03416
+C 2 .4E-3 2773.75849 2965.955234 376.9911185 2010.99049 -517.772984
+C -1493.21751 2010.990487 -517.772984 -1493.2175 .2755769E-5
+C 376.9911184 1.174129748 2010.99049 -517.772984 -1493.21751
+BLANK card ending selective variable output request (node voltages, here)
+C 350 .07 .7006894039 927.0509831 376.7455301 2408.782669 10873.00302
+C -13281.7857 -4598.11137 -807.600679 5405.712048 7006.894039
+C 376.7757426 1.169603437 2408.782669 10873.00302 -13281.7857
+C Variable max: 3027.62917 3000. 376.9914104 7182.444042 21231.90574
+C 2087.531085 11218.73045 2087.574976 12006.72539 11206.93469
+C 377.0003725 1.174129748 7182.444042 21231.90574 2087.531085
+C Times of max: .016 0.0 .0504 .0532 .0578
+C .0108 .0624 .0386 .0568 .0534
+C .0652 .0352 .0532 .0578 .0108
+ PRINTER PLOT
+ 194 8. 0.0 96. UM-1 TQGEN { Plot limits: (-0.913, 1.466)
+ 19415. 0.0 75. UM-1 OMEGM { Plot limits: (0.000, 3.770)
+ 194 8. 0.0 96. UM-1 IPA { Plot limits: (-1.335, 0.718)
+BLANK card ending batch-mode plot cards
+BEGIN NEW DATA CASE
+C 3rd of 3 subcases is added 12 November 2001. It is unrelated to preceding.
+C Data to be used to test counting of actual (minimal) table sizes. This is
+C ESTIMATE ACTUAL TABLE SIZES (EATS) which entered the UTPF 12 November 2001.
+C Data is simple, and was obtained from DC-7 by canibalization. Prior to
+C addition here, data was stored separately as COUNT.DAT This is just the
+C first illustration of EATS so keep it simple by omission of batch-mode
+C plot requests and other unrelated features.
+PRINTED NUMBER WIDTH, 9, 2, { Full precision on each of 8 columns of printout
+ .000025 .0007 60. 60.
+ 1 1 1 1 -1
+ 5 5 10 10 20 1
+ESTIMATE ACTUAL TABLE SIZES { New request must follow immediately the misc. data
+ 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
+ 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
+ 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
+ 10 10 10 10
+ 0 0 10
+ 10 10
+C The preceding data is similar to NEW LIST SIZES in that there is one entry
+C for each of 30 lists, with 10 per card. There are two such sets: first
+C the multiplication factors, and second the additive constants.
+ GENA SWA 89352. 3
+ BRANCH NAME:2nd LIN
+ GENB SWB GENA SWA 1
+ GENC SWC GENA SWA
+93RECA NAME 1st NL .559 300. 3
+ 0.0 0.0
+ .5590 300.
+ .9344 400.
+ 9999
+ BRANCH NAME:2nd NL ! { Hold lower case of this 2nd, but not following 3rd
+93RECB RECA .559 300. 4
+-1SENDA RECA .137681.07755.6806124.27
+-2SENDB RECB .03009.450289.5000124.27
+-3SENDC RECC
+-1RECA ENDA SENDA RECA
+-2RECB ENDB
+-3RECC ENDC
+BLANK card ends all branch cards
+ SWA SENDA -1. 1.0
+ SWB SENDB 0.0 1.0
+ SWC SENDC 0.0 1.0
+BLANK card ends all switch cards
+14GENA 188000. 60. 0.0 -1.
+14GENB 188000. 60. 120. -1.
+14GENC 188000. 60. -120. -1.
+BLANK card ending source cards
+ RECA RECB RECC
+BLANK card ending output variable requests (just node voltages, here)
+ PRINTER PLOT
+BLANK card terminating plot cards
+BEGIN NEW DATA CASE
+BLANK
+EOF
+
+ 10 June 2002, WSM adds output to the screen in case of DISK use.
+Without any EATS, this is simple as should be illustrated in the October
+(or later) newsletter. But with EATS, there are variations depending upon:
+1) the subcase number; and 2) whether the order for EATS comes from
+STARTUP, or is buried in data, or both. Consider first the case of no
+STARTUP request. I..e., assume FLZERO > 0. Then the screen will show:
+ ---- Begin next subcase number KNTSUB = 2
+ ---- Begin next subcase number KNTSUB = 3
+ Explicit EATS request now is being processed.
+I.e., the exceptional 3rd subcase will have two lines rather than
+the usual one. On the other hand, if FLZERO < 0, the screen
+should show:
+ ---- Begin EATS for subcase number KNTSUB = 1
+ ---- Begin EATS for subcase number KNTSUB = 2
+ ---- Both implied and explicit EATS. KNTSUB = 3
+
+ There is yet another variation. Suppose FLZERO > 0 with
+EATS data embedded in the 1st subcase. Output will differ from the
+preceding as follows:
+ ---- Explicit EATS request in subcase KNTSUB = 1