diff options
Diffstat (limited to 'benchmarks/dcn15.dat')
-rw-r--r-- | benchmarks/dcn15.dat | 484 |
1 files changed, 484 insertions, 0 deletions
diff --git a/benchmarks/dcn15.dat b/benchmarks/dcn15.dat new file mode 100644 index 0000000..02a602a --- /dev/null +++ b/benchmarks/dcn15.dat @@ -0,0 +1,484 @@ +BEGIN NEW DATA CASE
+C BENCHMARK DCNEW-15
+C Exhaustive test of PostScript output as received from Robert Meredith
+C of NYPA (the New York Power Authority) in White Plains. Prior to
+C being copied to a new DCN15 on 15 November 1995, this was separate
+C disk file PLOTTEST.DAT that creates 158-Kbyte .PS file as output
+C when NYMAX = 1024 and NXMAX = 1280 (the NYPA choices) are used.
+C January, 1996, newsletter should summarize associated changes.
+BEGIN NEW DATA CASE {using blank_card_skeleton and atp "/KEYWORD" sorting
+C RUN 4.75 CYCLES PAST ENERGIZATION AT .5 CY; ATTEMPT CLEAR 2.5 LATER AT 3
+C UNUSED OPTIONS DELETED/SUPPRESSED - SEE EENERG-40.DAT FOR MORE COMPLETE LIST
+C FREE FORMAT TIME STEP- 1000/CYCLE FOR 5.25 CYCLES = .0875 SEC
+C SHORTEN TO 1.65 CYCLES = .0275 SEC
+ .000016666666, .0875 , 60.000 , 0.,,,,,,,
+C PRN> PLT> NET> SS> MAX> SAVE> NENERG> >
+ 1 5 0 0 1 -1
+ 5 5 20 20 100 100 500 500
+TACS HYBRID {(from blank_card_skeleton.incs)
+C ANALYZE LISC CAPACITIVE INRUSH DURING E. GARDEN CITY A-GROUND FAULT
+C BY SUBTRACTING FAULT AND REACTOR CURRENTS FROM INRUSH IN TACS
+C TYPE 90 TACS SOURCES DERIVED FROM NETWORK VOLTAGES:
+C <NAME> <----A---><----A---><----A---> <T START ><T STOP >
+90BUSBV 0. 999.
+C TYPE 91 TACS SOURCES DERIVED FROM NETWORK SWITCH CURRENTS (1ST NODE)
+C <NAME> <----A---><----A---><----A---> <T START ><T STOP >
+C 4 SHUNT REACTOR CURRENTS (OUT OF LISC)
+91EGCHWX 0. 999.
+91EGCHWY 0. 999.
+91EGCHWZ 0. 999.
+91ISLNDX 0. 999.
+91ISLNDY 0. 999.
+91ISLNDZ 0. 999.
+91SPRB1X 0. 999.
+91SPRB1Y 0. 999.
+91SPRB1Z 0. 999.
+C FAULT CURRENT AT E. GARDEN CITY (USE CAUTION-LINE SWITCHES EXIST IF XFMRS)
+C ALSO OUT OF LISC
+91EGCHWA 0. 999.
+C INRUSH TO LISC AT SPRAIN BROOK (ENERGIZATION SWITCHES MUST COME FIRST)
+C THESE CURRENTS ARE INTO LISC
+91SPRBRA 0. 999.
+91SPRBRB 0. 999.
+91SPRBRC 0. 999.
+C FORTRAN STATEMENTS; 99= INPUT; 98= OUTPUT; 88= INSIDE
+C <NAME> =< FREE FORMAT FORTRAN TO COL 80 ----->
+C REACTOR TOTAL AMPS
+99REACTA = EGCHWX +ISLNDX +SPRB1X
+99REACTB = EGCHWY +ISLNDY +SPRB1Y
+99REACTC = EGCHWZ +ISLNDZ +SPRB1Z
+C CAPACITIVE CURRENT INTO LISC IS NET OF ABOVE; BY PHASE
+99CAPINA = SPRBRA -REACTA -EGCHWA
+99CAPINB = SPRBRB -REACTB
+99CAPINC = SPRBRC -REACTC
+C S-BLOCKS OF ORDER 1 IN COL 2 INTEGRATE VOLTAGES TO GET FLUXES (TIMES 250.0).
+C <NAME> +<NAME> +<NAME> +<NAME> +<NAME> +<NAME> <GAIN><FXLO><FXHI><NMLO><NMHI>
+C N0 & D0><N1 & D1 ><N2 & D2 ><N3 & D3 ><N4 & D4 ><N5 & D5 ><N6 & D6 ><N7 & D7 >
+C <NAME>CD+< IN1> +< IN2> +< IN3> +< IN4> +< IN5> < A >< B >< C >< D >< E >
+C TACS OUTPUT REQUESTS - TYPE 33
+C <NAME><NAME><NAME><NAME><NAME><NAME><NAME><NAME><NAME><NAME><NAME><NAME><TY33>
+33REACTA REACTB REACTC CAPINA CAPINB CAPINC BUSBV
+BLANK CARD ENDING ALL ATP-SORTED TACS CARDS (from blank_card_skeleton.incs)
+C SIMPLE LISC SHUNT REACTORS:
+$VINTAGE, 1
+C <NAME><NAME><----><---->RRRRRRRRRRRRRRRRXXXXXXXXXXXXXXXXCCCCCCCCCCCCCCCC P
+ EGCHWX 15.8 793.5
+ EGCHWY 15.8 793.5
+ EGCHWZ 15.8 793.5
+ ISLNDX 15.8 793.5
+ ISLNDY 15.8 793.5
+ ISLNDZ 15.8 793.5
+ SPRB1X 7.93 396.7
+ SPRB1Y 7.93 396.7
+ SPRB1Z 7.93 396.7
+$VINTAGE, 0
+C SIMPLE LISC MODEL
+$VINTAGE, 1
+C <NAME><NAME><----><---->RRRRRRRRRRRRRRRRXXXXXXXXXXXXXXXXCCCCCCCCCCCCCCCC P
+ SPRB1AMAINLA .4 2.
+ SPRB1BMAINLB .4 2.
+ SPRB1CMAINLC .4 2.
+ MAINLAISLNDA .3 1.
+ MAINLBISLNDB .3 1.
+ MAINLCISLNDC .3 1.
+ ISLNDAEGCHWA .4 2.
+ ISLNDBEGCHWB .4 2.
+ ISLNDCEGCHWC .4 2.
+C 200 MVAR AT MAINL FOR PIPE; 300 MVAR SPLIT FOR SCFF; 200 MVAR AT ISLND
+ MAINLA 4.45
+ MAINLA 3.34
+ ISLNDA 3.34
+ EGCHWA 4.45
+ MAINLB 4.45
+ MAINLB 3.34
+ ISLNDB 3.34
+ EGCHWB 4.45
+ MAINLC 4.45
+ MAINLC 3.34
+ ISLNDC 3.34
+ EGCHWC 4.45
+$VINTAGE, 0
+C OTHER CIRCUITS:
+C 10000 MVA DUNWOOD; 5000 MVA EASTVIEW; 5000 MVA W 49TH
+$VINTAGE, 1
+C <NAME><NAME><----><---->RRRRRRRRRRRRRRRRXXXXXXXXXXXXXXXXCCCCCCCCCCCCCCCC P
+ SRCDUASPRDUA .6 11.9
+ SRCDUBSPRDUB .6 11.9
+ SRCDUCSPRDUC .6 11.9
+ SRCEAASPREAA 1.2 23.8
+ SRCEABSPREAB 1.2 23.8
+ SRCEACSPREAC 1.2 23.8
+ SRCW4ASPRW4A 1.2 23.8
+ SRCW4BSPRW4B 1.2 23.8
+ SRCW4CSPRW4C 1.2 23.8
+$VINTAGE, 0
+C SIMPLE SPRAIN REACTORS:
+$VINTAGE, 1
+C <NAME><NAME><----><---->RRRRRRRRRRRRRRRRXXXXXXXXXXXXXXXXCCCCCCCCCCCCCCCC P
+ SPX5SA 3.17 158.7
+ SPX5SB 3.17 158.7
+ SPX5SC 3.17 158.7
+C DUMMY BUS TO DERIVE A UNIQUE SPRAIN BROOK PHASE B VOLTAGE FOR TACS
+ SPRBRABUSBV 1.0
+$VINTAGE, 0
+BLANK CARD ENDING ALL ATP-SORTED BRANCH CARDS (from blank_card_skeleton.incs)
+C ********************************************* STUDY-DEPENDENT CABLE SWITCHING:
+C SWITCH CARD: COL 1-2 IS 0 FOR ORDINARY & GAUSS. STATISTICS SWITCHES, NOT TACS.
+C CLOSING, OPENING TIMES AND STATISTICS PARAMETERS BELOW ARE IN SECONDS.
+C <NAME><NAME><T CLOSE ><T. OPEN ><AMP MARG> 67890123 MEASURING 56789012345678 P
+C <NAME><NAME><GAUS AVG><GAUS SIG><AMP MARG> STATISTICS P
+C THREE PHASE ENERGIZATION FROM SPRAIN BROOK AT 180 DEGREES
+C ATTEMPT OPEN AT 3 CY
+ SPRBRASPRB1A .0083333 .05 1. 1
+ SPRBRBSPRB1B .0083333 .05 1. 1
+ SPRBRCSPRB1C .0083333 .05 1. 1
+C <NAME><NAME><T CLOSE ><T. OPEN ><AMP MARG> 67890123 MEASURING 56789012345678 P
+C A PHASE FAULT AT E. GARDEN CITY CABLE
+ EGCHWA MEASURING 1
+C *************************************************** CABLE CROSSING COMPONENTS:
+C ANALYSIS OF LISC INRUSH COMPONENTS:
+C MONITORING SIMPLE LISC SHUNT REACTORS:
+C <NAME><NAME><T CLOSE ><T. OPEN ><AMP MARG> 67890123 MEASURING 56789012345678 P
+ EGCHWAEGCHWX MEASURING 1
+ EGCHWBEGCHWY MEASURING 1
+ EGCHWCEGCHWZ MEASURING 1
+ ISLNDAISLNDX MEASURING 1
+ ISLNDBISLNDY MEASURING 1
+ ISLNDCISLNDZ MEASURING 1
+ SPRB1ASPRB1X MEASURING 1
+ SPRB1BSPRB1Y MEASURING 1
+ SPRB1CSPRB1Z MEASURING 1
+C MONITORING OTHER CIRCUITS:
+C <NAME><NAME><T CLOSE ><T. OPEN ><AMP MARG> 67890123 MEASURING 56789012345678 P
+ SPRDUASPRBRA MEASURING 1
+ SPRDUBSPRBRB MEASURING 1
+ SPRDUCSPRBRC MEASURING 1
+ SPREAASPRBRA MEASURING 1
+ SPREABSPRBRB MEASURING 1
+ SPREACSPRBRC MEASURING 1
+ SPRW4ASPRBRA MEASURING 1
+ SPRW4BSPRBRB MEASURING 1
+ SPRW4CSPRBRC MEASURING 1
+C MONITORING SIMPLE SPRAIN REACTORS:
+C <NAME><NAME><T CLOSE ><T. OPEN ><AMP MARG> 67890123 MEASURING 56789012345678 P
+ SPRBRASPX5SA MEASURING 1
+ SPRBRBSPX5SB MEASURING 1
+ SPRBRCSPX5SC MEASURING 1
+BLANK CARD ENDING ALL ATP-SORTED SWITCH CARDS (from blank_card_skeleton.incs)
+C VOLTAGE SOURCES BEHIND SIMPLE LINES:
+C *= VOLTAGE IF POSITIVE; CURRENT IF NEGATIVE
+C <NAME> <CRESTVAL><FREQ ><ANGLE > <T START ><T STOP >
+14SRCDUA 1 281691. 60. 0. -1.0
+14SRCDUB 1 281691. 60. -120. -1.0
+14SRCDUC 1 281691. 60. - 70. -1.0
+14SRCEAA 1 281691. 60. 0. -1.0
+14SRCEAB 1 281691. 60. -120. -1.0
+14SRCEAC 1 281691. 60. - 70. -1.0
+14SRCW4A 1 281691. 60. 0. -1.0
+14SRCW4B 1 281691. 60. -120. -1.0
+14SRCW4C 1 281691. 60. - 70. -1.0
+BLANK CARD ENDING ALL ATP-SORTED SOURCE CARDS (from blank_card_skeleton.incs)
+C <BUS ><VOLT><MON.><FOR ><NODE>< >< >< >< >< >< >< >< >
+ SPRBRA SPRBRB SPRBRC EGCHWA EGCHWB EGCHWC
+C First 6 output variables are electric-network voltage differences (upper
+C Next 25 output variables are branch currents (flowing from the upper nod
+C Next 7 output variables belong to TACS (with "TACS" an internally-added
+C Step Time SPRBRA SPRBRB SPRBRC EGCHWA EGCHWB EGCHWC
+C
+C
+C EGCHWA EGCHWB EGCHWC ISLNDA ISLNDB ISLNDC
+C EGCHWX EGCHWY EGCHWZ ISLNDX ISLNDY ISLNDZ
+C
+C SPRDUB SPRDUC SPREAA SPREAB SPREAC SPRW4A
+C SPRBRB SPRBRC SPRBRA SPRBRB SPRBRC SPRBRA
+C
+C SPRBRC TACS TACS TACS TACS TACS
+C SPX5SC REACTA REACTB REACTC CAPINA CAPINB
+C Phasor I(0) = 0.0000000E+00 Switch "EGCHWA" to " " closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "EGCHWA" to "EGCHWX" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "EGCHWB" to "EGCHWY" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "EGCHWC" to "EGCHWZ" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "ISLNDA" to "ISLNDX" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "ISLNDB" to "ISLNDY" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "ISLNDC" to "ISLNDZ" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "SPRB1A" to "SPRB1X" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "SPRB1B" to "SPRB1Y" closed in the
+C Phasor I(0) = 0.0000000E+00 Switch "SPRB1C" to "SPRB1Z" closed in the
+C Phasor I(0) = 1.8020056E+01 Switch "SPRDUA" to "SPRBRA" closed in the
+C Phasor I(0) = -7.4949973E+02 Switch "SPRDUB" to "SPRBRB" closed in the
+C Phasor I(0) = -7.9731518E+02 Switch "SPRDUC" to "SPRBRC" closed in the
+C Phasor I(0) = 9.0100278E+00 Switch "SPREAA" to "SPRBRA" closed in the
+C Phasor I(0) = -3.7474986E+02 Switch "SPREAB" to "SPRBRB" closed in the
+C Phasor I(0) = -3.9865759E+02 Switch "SPREAC" to "SPRBRC" closed in the
+C Phasor I(0) = 9.0100278E+00 Switch "SPRW4A" to "SPRBRA" closed in the
+C Phasor I(0) = -3.7474986E+02 Switch "SPRW4B" to "SPRBRB" closed in the
+C Phasor I(0) = -3.9865759E+02 Switch "SPRW4C" to "SPRBRC" closed in the
+C Phasor I(0) = 3.6040111E+01 Switch "SPRBRA" to "SPX5SA" closed in the
+C Phasor I(0) = -1.4989995E+03 Switch "SPRBRB" to "SPX5SB" closed in the
+C Phasor I(0) = -1.5946304E+03 Switch "SPRBRC" to "SPX5SC" closed in the
+C 0 0.0 271505.166 -135494. 93140.8164 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C -749.49973 -797.31518 9.01002785 -374.74986 -398.65759 9.01002785
+C -1594.6304 0.0 0.0 0.0 0.0 0.0
+C 1 .16667E-4 271497.931 -134010.58 94739.6338 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C -752.0737 -795.35514 11.6960229 -376.03685 -397.67757 11.6960229
+C -1590.7112 0.0 0.0 0.0 0.0 0.0
+BLANK CARD ending output requests
+C 5250 .0875 344649.527 191299.527 323640.302 0.0 -47145.895 198177.748
+C 0.0 -481.43288 -381.56041 7.33790777 -482.30918 -382.59923
+C -406.62434 315.059242 422.024548 -203.31217 157.529621 422.024548
+C 630.115247 53.1490298 -1931.3137 -1533.2089 667.309594 1931.31368
+C Var maxima: 616453.613 329566.742 345463.852 0.0 406069.593 394188.344
+C 0.0 543.895482 530.803784 67.0966974 542.272824 529.035963
+C 1967.10962 1126.57279 6928.95568 983.554811 563.286397 6928.95568
+C 1842.77914 396.264811 2155.88852 2102.39918 3263.3985 4668.06408
+C Times max : .066666664 .038716665 .053233331 0.0 .056549998 .054416664
+C 0.0 .060783331 .058666664 .037849998 .060799998 .058683331
+C .00905 .022149999 .020933332 .00905 .022149999 .020933332
+C .023983332 .054149998 .060799998 .058666664 .009433333 .016233333
+C Var minima: -616441.36 -328926.65 -344125.86 0.0 -391677.76 -380868.54
+C 0.0 -601.24473 -655.23512 -71.518615 -601.0409 -654.05062
+C -2812.3738 -2427.7615 -6394.8627 -1406.1869 -1213.8807 -6394.8627
+C -1728.9227 -417.04027 -2395.2787 -2605.0808 -3285.1431 -5318.9546
+C Times min : .07498333 .029766665 .061583331 0.0 .065483331 .063366664
+C 0.0 .034366665 .015183333 .012383333 .034366665 .015216666
+C .018033333 .016716666 .045366665 .018033333 .016716666 .045366665
+C .015316666 .0124 .034383332 .015233333 .0087 .010816666
+ 2 Fault Current to Ground
+ Sprain Brook Energization of Lisc at 180 Degrees; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES--------+
+ EGCHWA
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2SPRAIN BROOK REACTOR CURRENT VS VOLTAGE - PHASE B
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT 0.5 -1.5 CYCLE TIME PLOTTED
+C
+C X-Y PLOT <-X AXIS LABEL----->
+ X-Y PLOT Phase B bus voltage(!!!)
+C LENX >< XMIN >< XMAX >
+ 10. -250.E3 250.E3
+C LENY >< YMIN >< YMAX ><DIV/IN> last defaults to 10 if zero
+ 8. -2000. 2000. 0.
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS AND TACS
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC.
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C FOR X-Y BRANCHES USE 12 COL(25-36) FOR X VAR; NEXT 12 FOR Y VARIABLE
+C FOR X-Y NODE VOLTS USE 6 COL(25-30) FOR X VAR; NEXT 6 FOR Y VARIABLE
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4>
+ 192 0.5 1.5 -.4E6.4E6TACS BUSBV SPRB1BSPRB1YLISC STUDY REACT CURRENT--+
+C *******************************************************************************
+ 2 CURRENTS INTO LISC AT SPRAIN BROOK 345 KV
+ SPRAIN BROOK ENERGIZATION OF (LISC) AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ Last word ends in 2 slashes\\
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES123
+ SPRBRASPRB1ASPRBRBSPRB1BSPRBRCSPRB1C
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 VOLTAGES AT SPRAIN BROOK 345 KV BUS
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ new border=(\/(\/(\/(\/(\/\/\/\/\/\/\/\/\/\/)\/)\/)\/)\/)
+ new border =(\/(\/(\/(\/(\/\/\/\/\/\/\/\/\/\/)\/)\/)\/)\/)
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 145 -.4E6.4E6BRANCH Lisc Study Volts
+ SPRBRASPRBRBSPRBRC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 5000. 5000. 55000.
+C *****************************************************************************
+ 2 VOLTAGES AT E. GARDEN CITY 345 KV CABLE
+ new border=)/\)/\)/\)/\)/\/\/\/\/\/\/\(/\(/\(/\(/\(
+ new border =)/\)/\)/\)/\)/\/\/\/\/\/\/\(/\(/\(/\(/\(
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT )SECONDS SCALE ///\\\ <3 EACH
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 143 -.4E6.4E6BRANCH LISC STUDY VOLTS
+ EGCHWAEGCHWBEGCHWC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.01 .01 .11
+C *****************************************************************************
+ 2 PHASE A CURRENTS INTO LISC: REACT INRUSH, CAP INRUSH, FAULT, TOTAL
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPS ((((OK?))))
+ TACS REACTATACS CAPINAEGCHWA SPRBRASPRB1A
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 PHASE B CURRENTS INTO LISC: REACT INRUSH, CAP INRUSH, TOTAL
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES
+ TACS REACTBTACS CAPINBSPRBRBSPRB1B
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 PHASE C CURRENTS INTO LISC: REACT INRUSH, CAP INRUSH, TOTAL
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES
+ TACS REACTCTACS CAPINCSPRBRCSPRB1C
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 CURRENTS INTO SPRAIN BROOK FROM 4 EASTVIEW CKTS
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES
+ SPREAASPRBRASPREABSPRBRBSPREACSPRBRC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 CURRENTS INTO SPRAIN BROOK FROM W 49TH CKTS
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH LISC STUDY AMPERES
+ SPRW4ASPRBRASPRW4BSPRBRBSPRW4CSPRBRC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 CURRENTS INTO SPRAIN BROOK FROM DUNWOODIE 345 KV CKT
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH
+ SPRDUASPRBRASPRDUBSPRBRBSPRDUCSPRBRC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 CURRENTS INTO SPRAIN BROOK FROM 750 MVA OF NON-LINEAR SHUNT REACTORS
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH
+ SPX5SASPRBRASPX5SBSPRBRBSPX5SCSPRBRC
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2 PHASE A CURRENTS INTO SPRAIN BR.: EASTV, W49TH, DUNWD, SHUNT REACT
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT
+C
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS,TACS,FREQ SCAN
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC; 6 FOR HERTZ; 7 FOR LOG HERTZ
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4><BR3A><BR3B><BR4A><BR4B>
+ 192 -.4E6.4E6BRANCH
+ SPREAASPRBRASPRW4ASPRBRASPRDUASPRBRASPX5SASPRBRA
+C SCALE PER INCH<TIME UNIT START<TIME UNIT END ><VERT MIN ><VERT MAX >
+ 0.5 .25 5.25
+C *****************************************************************************
+ 2SPRAIN BROOK REACTOR CURRENT VS VOLTAGE - PHASE B
+ SPRAIN BROOK ENERGIZATION OF LISC AT 180 DEGREES; 4 SHUNT REACTORS ON
+ INTO A-PHASE-TO-GROUND FAULT AT E. GARDEN CITY CABLE; CBS OPEN 2.5 CY LATER
+ CASE PLOTTEST.DAT 0.5 -1.5 CYCLE TIME PLOTTED
+C
+C X-Y PLOT <-X AXIS LABEL----->
+ X-Y PLOT PHASE B BUS VOLTAGE
+C LENX >< XMIN >< XMAX >
+ 10. -250.E3 250.E3
+C LENY >< YMIN >< YMAX ><DIV/IN> last defaults to 10 if zero
+ 8. -2000. 2000. 0.
+C COL 3 IS 4 FOR NODE VOLTS;8 FOR BRANCH VOLTS;9 FOR AMPS AND TACS
+C COL 4 IS 2 FOR CYCLES; 5 FOR MICROSEC.
+C COL 5-7 ARE BLANK TO INDICATE EXTENDED PRECISION OF PLOT SCALES, ETC.
+C WRITE "BRANCH" STARTING IN FIRST NODE COL FOR PLOTTING OF UP TO 4 BRANCHES
+C FOR X-Y BRANCHES USE 12 COL(25-36) FOR X VAR; NEXT 12 FOR Y VARIABLE
+C FOR X-Y NODE VOLTS USE 6 COL(25-30) FOR X VAR; NEXT 6 FOR Y VARIABLE
+C CAN ALSO LABEL ON 4-NODE OR 'BRANCH' CARD: <GRAPH HEADING ><VERT AX. LABEL>
+C 34S/"<TST<TSP<LLMT<ULT<NOD1><NOD2><NOD3><NOD4>
+ 192 0.5 1.5 -.4E6.4E6TACS BUSBV SPRB1BSPRB1YLISC STUDY))))))REACT CURRENT\\\
+BLANK CARD ENDING plot cards
+BEGIN NEW DATA CASE
+BLANK
|