diff --git a/benchmarks/dc31.dat b/benchmarks/dc31.dat new file mode 100644 index 0000000..4b6aa3d --- /dev/null +++ b/benchmarks/dc31.dat @@ -0,0 +1,486 @@ +BEGIN NEW DATA CASE
+C BENCHMARK DC-31
+C Simulation of single-line-to-ground-fault on the open receiving end of the
+C single-circuit, 138-mile, 500-kV overhead line that connects "John Day"
+C with "lower monumental" (BPA substations). Semlyen representation from
+C DC-29 is used for the line. See DCNEW-4 for the corresponding Marti
+C simulation. See Rule Book Ref. 3 for further description. Yet observe
+C that source angles and the instant of fault initiation do not correspond.
+C There are a total of 3 subcases, with two following unrelated to this
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+ .000050 .050 60. 60.
+ 1 1 1 1 1 -1
+ 5 5 20 20 100 100
+ JDGA JDA 14. 1
+ JDGB JDB 14.
+ JDGC JDC 14.
+C L= 138.0MILES, RHO= 27.0, SS FREQ= 60.00, NSS=0, KFIT= 0, KPS=2, KYC=10
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 3.3636 .05215 4 1.602 19.25 50. 50.
+C 3.3636 .05215 4 1.602 20.75 50. 50.
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C
+C 27. 5000. 1 138.
+C 27. 60.00 1 138.
+C 27. 6.00 1 138. 6 20
+C
+-1JDA LMA 0.55456E-02 0.77998E-03 1 1 2 2 3
+ 0.14938602E+02 0.90516313E+02-0.16261865E-03 0.14500324E-02 0.60000000E+02
+ 0.00000E+00 0.15161E+05 0.75119E+00 0.00000E+00 0.17105E+04 0.24881E+00
+ 0.00000E+00 0.59584E+03-0.11954E-02 0.00000E+00 0.39933E+05-0.74162E-03
+-1JDB LMB 0.74392E-02 0.74149E-03 2 2 2 2 3
+ 0.83801231E+00 0.38634735E+02-0.44536501E-04 0.20637999E-02 0.60000000E+02
+ 0.00000E+00 0.26608E+06 0.83767E+00 0.00000E+00 0.35627E+05 0.16233E+00
+ 0.00000E+00 0.13630E+03-0.49171E-03 0.00000E+00 0.32940E+05-0.75349E-04
+-1JDC LMC 0.42823E-02 0.74017E-03 3 3 2 2 3
+ 0.26535168E+01 0.67894100E+02-0.45225808E-04 0.11682248E-02 0.60000000E+02
+ 0.00000E+00 0.61698E+06 0.90903E+00 0.00000E+00 0.15239E+05 0.90969E-01
+ 0.00000E+00 0.25667E+03-0.34465E-03 0.00000E+00 0.11831E+05-0.28233E-04
+ 0.10000E+01 0.00000E+00 0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.71114E+00 0.00000E+00-0.41983E-15 0.00000E+00 0.10000E+01 0.00000E+00
+ 0.10000E+01 0.00000E+00-0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00 0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+ 0.22471E+00 0.00000E+00-0.27373E-15 0.00000E+00 0.84054E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00-0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+C Note: the preceding branch cards are old. If produced by SEMLYEN SETUP
+C on or after 27 November 2000, the low precision [Tv] and [Ti] would
+C be replaced by high precision for the real parts only. This can be
+C seen from current output of DC-29. 6E12.5 ---> 3E26.18 We retain
+C the old branch cards in this subcase to demonstrate that such old data
+C continues to remain compatible. See NO IMAGINARY PART as is being
+C written about for the April, 2001, newsletter. To see use of the new
+C wide format for [Tv] and [Ti], see DC-62.
+ TOWER 2.0
+BLANK card ending branch cards
+ LMA TOWER .00433 1.0 1
+BLANK card terminating all switch cards
+14JDGA 303000. 60. -90. -1.
+14JDGB 303000. 60. -210. -1.
+14JDGC 303000. 60. 30. -1.
+BLANK card ending all source cards
+C Total network loss P-loss by summing injections = -4.779046825640E+06
+C Last inject: JDGC 262405.69734669 303000. -173.5167762169 331.67972792735
+C Last inject: 151500. 30.0000 282.67184205232 121.5434868
+ LMA LMB LMC JDA JDC
+C Step Time LMA LMB LMC JDA JDC
+C
+C 0 0.0 1571.475581 -276456.932 278765.7622 153.7361338 266363.1031
+C 1 .5E-4 7630.423588 -279401.215 275709.5695 5941.026761 263392.9685
+C 2 .1E-3 13684.53899 -282253.973 272563.1515 11741.29345 260360.8975
+C 3 .15E-3 19733.66162 -285005.65 269320.0035 17534.50579 257232.6923
+BLANK card ending output variable requests
+C Last step begins: 1000 .05 -4383.86263 -267262.886 294635.7149
+C Last step continue ..... : -3765.02773 266358.2578 -2191.93132 -2002.40336
+C Variable max : 321290.8039 382325.3516 420199.3815 307502.4578 313056.9229
+C Times of max : .00415 .0271 .015 .00415 .01555
+C Variable min : -4633.97345 -375865.379 -529913.225 -303202.542 -357915.083
+C Times of min : .01665 .01825 .0061 .01245 .00685
+ PRINTER PLOT { Axis limits: (-5.299, 4.202)
+ 2Simulation of fault at Lower Monumental end of 138-mile line to John Day.
+ 1 SMOOTH
+ PRINT HEAD OFF
+ Voltage at Lower Monumental, where "a"-phase is faulted at 4.33 msec.
+ 144 2. 0.0 20. LMA LMB LMC Lower Mon. Fault voltage in volt
+BLANK card ending all plot cards
+BEGIN NEW DATA CASE
+C 2nd of 3 data subcases is unrelated to the 1st. 3rd will be compared with it
+C 1973 GPU Stolle Road to Homer City line energization without surge arresters
+C These extra two cases are added to document Prof. Xusheng Chen's transformer
+C as described in January, 1993, newsletter.
+ .000050 .050 60. 60. { Increase deltat from 25 microsecs of '70s
+ 100 1 0 0 1
+ SORA GARA 3.06
+ SORB GARB 3.06
+ SORC GARC 3.06
+-1GARA ST1A .6109 2.3280 3.02 12.44
+-2GARB ST1B .1278 .79260 5.36 12.44
+-3GARC ST1C
+ 1GARA ERIA 6.2245
+ 2GARB ERIB 2.4289 6.2245
+ 3GARC ERIC 2.4289 2.4289 6.2245
+ 1GARA DAVA 21.905
+ 2GARB DAVB 10.465 21.905
+ 3GARC DAVC 10.465 10.465 21.905
+-1ERIA ST1A .6701 2.3608 3.02 10.70
+-2ERIB ST1B .1000 .71960 5.36 10.70
+-3ERIC ST1C
+-1ROLA ST1A .6342 2.3507 3.02 20.27
+-2ROLB ST1B .1005 .72150 5.36 20.27
+-3ROLC ST1C
+-1DAVA ST1A .6641 2.3641 3.02 14.53
+-2DAVB ST1B .0998 .71990 5.36 14.53
+-3DAVC ST1C
+ TRANSFORMER 21.3 249.1TRANA 1
+ 21.3 249.1
+ 99.8 274.0
+ 236.9 288.9
+ 1602. 326.3
+ 9999.
+ 1SWPA 0.0 -1.11 115.
+ 2ST3A 0.0 39.4 345.
+ 3T-A T-B 0.0 1.24 59.75
+ TRANSFORMER TRANA TRANB 1
+ 1SWPB
+ 2ST3B
+ 3T-B
+ TRANSFORMER TRANA TRANC 1
+ 1SWPC
+ 2ST3C
+ 3 T-A
+-1ST3A HOMA .6129 1.9245 4.50 214.0
+-2ST3B HOMB .0502 .59410 7.05 214.0
+-3ST3C HOMC
+ ST3A 96514. 1930.
+ ST3B 96514. 1930.
+ ST3C 96514. 1930.
+ ST3A 12.82
+ ST3B 12.82
+ ST3C 12.82
+ SWPA 37.70
+ SWPB 37.70
+ SWPC 37.70
+C 24 July 2008, add a disconnected Type-51, 52 branch that has very low
+C impedance. The [R] and [L] matrices are perfectly invertible; in fact, for
+C simplicity, we make them diagonal. Prior to improvement of REDUCT, the
+C ATP response was to halt execution. The small numbers made ATP think that
+C the matrix was singular. A 40-year-old weakness was just noticed (amazing):
+C ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ERROR/ ...
+C KILL code number Overlay number Nearby statement number
+C 86 13 4233
+C KILL = 86. Singularity has been detected within SUBROUTINE REDUCT ...
+51SORA 1.E-19 1.E-19 { R(1,1) = L(1,1) = 1.E-19
+52EXTRA 0.0 0.01.E-19 1.E-19 { R(2,1) = L(2,1) = 0
+ EXTRA 1.0 { Let the secondary drive a 1-ohm resistor
+BLANK card ending all branch cards
+ ST1A SWPA .007940 1.0
+ ST1B SWPB .007940 1.0
+ ST1C SWPC .007940 1.0
+BLANK card ending all switch cards
+14SORA 93800. 60. 185. -1.0
+14SORB 93800. 60. 65. -1.0
+14SORC 93800. 60. -55. -1.0
+C Total network loss P-loss by summing injections = 2.199610000000E+28
+C This extraordinary phasor loss is due to that extra Type-51, 52 branch,
+C which is nearly a short circuit. Without it, loss is 4.805637702155E+02
+BLANK card ending all source cards
+ SWPA SWPB SWPC ST3A ST3B ST3C HOMA HOMB HOMC SWPA SWPB SWPC
+C Step Time SWPA SWPB SWPC ST3A ST3B
+C
+C HOMC SWPA SWPB SWPC TRANA
+C TERRA
+C 0 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0
+C 100 .005 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0
+C *** Close switch "ST1A " to "SWPA " after 7.95000000E-03 sec.
+C *** Close switch "ST1B " to "SWPB " after 7.95000000E-03 sec.
+C *** Close switch "ST1C " to "SWPC " after 7.95000000E-03 sec.
+C 200 .01 74055.64255 1496.684511 -75552.3271 217501.3182 -11199.8796
+C -202295.843 74055.64255 1496.684511 -75552.3271 11.60842824
+BLANK card ending selective node voltage output requests
+C 1000 .05 -41438.1417 14616.52552 4941.023887 -74849.3547 24242.7193
+C -300362.665 -41438.1417 14616.52552 4941.023887 -.003640141
+C Variable max : 169590.981 140542.9342 130439.2455 610291.9724 509791.1645
+C 761896.4358 169590.981 140542.9342 130439.2455 1615.403803
+C Times of max : .04255 .02965 .03775 .0425 .02945
+C .03865 .04255 .02965 .03775 .02875
+C Variable min : -156192.014 -132716.009 -161788.345 -534753.351 -467406.362
+C -777439.086 -156192.014 -132716.009 -161788.345 -43.1002572
+C Times of min : .016 .04015 .04285 .0161 .04065
+C .0427 .016 .04015 .04285 .03875
+ PRINTER PLOT
+ 144 5. 0.0 50. HOMA { Axis limits: (-7.642, 8.522)
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 3rd of 3 data subcases is the same as the 2nd except for 3-phase transformer
+C 1973 GPU Stolle Road to Homer City line energization without surge arresters
+C These extra two cases are added to document Prof. Xusheng Chen's transformer
+C as described in the January and April, 1993, issues of the newsletter. The
+C case came from Prof. Chen as disk file MDD6A.DAT on a floppy dated May 20,
+C 1993 (this replaces the original 3rd subcase that was created 31 Mar 1993)
+C July, 1995, Prof. Chen replaces his XFCHEN, and answers change. The
+C old data case will be copied below as comments of this one are updated.
+PRINTED NUMBER WIDTH, 11, 1, { Request default precision (cancel [13,2] of 1st)
+C 4 May 2007, add following $PREFIX to allow remote execution.
+C Without this, the following DC31CHEN.DAT would not be found.
+$PREFIX, [] { $INCLUDE files are located in same place as this main data file
+USE SEATTLE XFORMER, dc31chen.dat ! { (hold lower case)
+C 1973 GPU Stolle Road to Homer City line energization with surge arresters
+ .000050 .050 60. 60. { Decrease Tmax from .200 to .050 for speed
+ 100 1 1 1 1
+$VINTAGE, 1
+ 1SWPA 5171.1723633
+ 2SWPB -1.2218941
+ 5171.4155273
+ 3SWPC -0.0011917
+ -1.2218941
+ 5171.1723633
+ 4ST3A 15511.6093750
+ -3.6675410
+ -0.0035769
+ 46558.4257813
+ 5ST3B -3.6675410
+ 15512.3398438
+ -3.6675410
+ -11.0082035
+ 46560.6210938
+ 6ST3C -0.0035769
+ -3.6675410
+ 15511.6093750
+ -0.0107361
+ -11.0082035
+ 46558.4296875
+$VINTAGE, 0
+ SORA GARA 3.06
+ SORB GARB 3.06
+ SORC GARC 3.06
+-1GARA ST1A .6109 2.3280 3.02 12.44
+-2GARB ST1B .1278 .79260 5.36 12.44
+-3GARC ST1C
+ 1GARA ERIA 6.2245
+ 2GARB ERIB 2.4289 6.2245
+ 3GARC ERIC 2.4289 2.4289 6.2245
+ 1GARA DAVA 21.905
+ 2GARB DAVB 10.465 21.905
+ 3GARC DAVC 10.465 10.465 21.905
+-1ERIA ST1A .6701 2.3608 3.02 10.70
+-2ERIB ST1B .1000 .71960 5.36 10.70
+-3ERIC ST1C
+-1ROLA ST1A .6342 2.3507 3.02 20.27
+-2ROLB ST1B .1005 .72150 5.36 20.27
+-3ROLC ST1C
+-1DAVA ST1A .6641 2.3641 3.02 14.53
+-2DAVB ST1B .0998 .71990 5.36 14.53
+-3DAVC ST1C
+-1STTA HOMA .6129 1.9245 4.50 214.0
+-2STTB HOMB .0502 .59410 7.05 214.0
+-3STTC HOMC
+ ST3A STTA .3737
+ ST3B STTB .3737
+ ST3C STTC .3737
+ ST1A SWIA .0415
+ ST1B SWIB .0415
+ ST1C SWIC .0415
+ ST3A 96514. 1930.
+ ST3B 96514. 1930.
+ ST3C 96514. 1930.
+C ST3A 12.82
+C ST3B 12.82
+C ST3C 12.82
+C SWPA 37.70
+C SWPB 37.70
+C SWPC 37.70
+BLANK card ending all branch cards
+ SWIA SWPA .007940 1.0 1
+ SWIB SWPB .007940 1.0 1
+ SWIC SWPC .007940 1.0 1
+BLANK card ending all switch cards
+14SORA 93800. 60. 185. -1.0
+14SORB 93800. 60. 65. -1.0
+14SORC 93800. 60. -55. -1.0
+C SWPA |TERRA *SWIA *
+C SWPB |TERRA *SWIB *
+C SWPC |TERRA *SWIC *
+C ST3A |TERRA *TERRA *STTA *
+C ST3B |TERRA *TERRA *STTB *
+C ST3C |TERRA *TERRA *STTC *
+C < < Etc. (many more rows) > >
+BLANK card ending all source cards
+ ST3A ST3B ST3C HOMA HOMB HOMC SWPA SWPB SWPC
+C Total network loss P-loss by summing injections = 4.805638098099E+02
+C
+C Last gen: SORC 53801.469729728 93800. 23.911871905618 29.188614218823
+C -76836.46175431 -55.0000000 16.739103380547 34.9932955
+C
+C Step Time ST3A ST3B ST3C HOMA HOMB HOMC
+C SWPA
+C SWIB SWIC CHEN CHEN CHEN CHEN
+C SWPB SWPC CURR1 FLUX1 CURR2 FLUX2
+C
+C CHEN CHEN CHEN CHEN
+C CURR5 FLUX5 CURR6 FLUX6
+C
+C 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0
+C 100 .005 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0
+C *** Close switch "SWIA " to "SWPA " after 7.95000000E-03 sec.
+C *** Close switch "SWIB " to "SWPB " after 7.95000000E-03 sec.
+C *** Close switch "SWIC " to "SWPC " after 7.95000000E-03 sec.
+C 200 .01 217332.128 -10970.216 -206361.84 310904.168 -111381.16 -199522.71
+C -104.3596 -2103.8643 2208.14107 .734567091 -104.35883 -.18046553
+C 34.0316806 -.17536706 699.245277 -.45094228
+BLANK card ending selective node voltage output requests
+C 1000 .05 -211428.33 122613.646 43085.5698 51552.1935 258779.757 51350.5473
+C 2076.8918 -1044.8039 -3514.8485 .441798215 2076.84637 2.27394289
+C 137.474393 2.17231652 -246.32711 -2.0030124
+C maxima : 791162.883 546834.494 590200.117 .1071971E7 702018.441 729565.112
+C 3811.90247 3682.98877 5102.5908 1.80215502 3811.88565 2.50132928
+C 1378.6839 2.50169355 1701.78362 1.00436763
+C Times of max : .04105 .02885 .0376 .0411 .0302 .0383
+C .0269 .03635 .0392 .01325 .0269 .0168
+C .01645 .01675 .02525 .03995
+C minima : -551969.66 -479168.62 -639520.52 -763493.9 -536730.14 -925214.16
+C -2538.3534 -5096.1259 -5475.4983 -1.8608421 -2538.2686 -.6020437
+C -1273.8113 -.78766225 -1930.5746 -2.5080431
+C Times of min : .01535 .03985 .0277 .0372 .01835 .0277
+C .02305 .02525 .0428 .03765 .02305 .0267
+C .0269 .02675 .0291 .01415
+ PRINTER PLOT
+C For a CALCOMP (vector) plot like Fig. MVI-1 on page 20 of the Ammendment to
+C the final report (Ammendment dated 23 May 1993), use this plot card:
+C 144 5. 0.0 50. ST3A ST3B ST3C High voltages Voltages, V
+ 144 2. 0.0 20. ST3A { Axis limits: (-5.520, 3.941)
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+BLANK
+EOF
+
+
+
+C 3rd of 3 data subcases is the same as the 2nd except for 3-phase transformer
+C 1973 GPU Stolle Road to Homer City line energization without surge arresters
+C These extra two cases are added to document Prof. Xusheng Chen's transformer
+C as described in the January and April, 1993, issues of the newsletter. The
+C case came from Prof. Chen as disk file MDD6A.DAT on a floppy dated May 20,
+C 1993 (this replaces the original 3rd subcase that was created 31 Mar 1993)
+PRINTED NUMBER WIDTH, 11, 1, { Request default precision (cancel [13,2] of 1st)
+USE SEATTLE XFORMER, DC31CHEN.DAT
+C 1973 GPU Stolle Road to Homer City line energization with surge arresters
+ .000050 .050 60. 60. { Decrease Tmax from .200 to .050 for speed
+ 100 1 1 1 1
+$VINTAGE, 1
+ 1SWPA 5171.1723633
+ 2SWPB -1.2218941
+ 5171.4155273
+ 3SWPC -0.0011917
+ -1.2218941
+ 5171.1723633
+ 4ST3A 15511.6093750
+ -3.6675410
+ -0.0035769
+ 46558.4257813
+ 5ST3B -3.6675410
+ 15512.3398438
+ -3.6675410
+ -11.0082035
+ 46560.6210938
+ 6ST3C -0.0035769
+ -3.6675410
+ 15511.6093750
+ -0.0107361
+ -11.0082035
+ 46558.4296875
+$VINTAGE, 0
+ SORA GARA 3.06
+ SORB GARB 3.06
+ SORC GARC 3.06
+-1GARA ST1A .6109 2.3280 3.02 12.44
+-2GARB ST1B .1278 .79260 5.36 12.44
+-3GARC ST1C
+ 1GARA ERIA 6.2245
+ 2GARB ERIB 2.4289 6.2245
+ 3GARC ERIC 2.4289 2.4289 6.2245
+ 1GARA DAVA 21.905
+ 2GARB DAVB 10.465 21.905
+ 3GARC DAVC 10.465 10.465 21.905
+-1ERIA ST1A .6701 2.3608 3.02 10.70
+-2ERIB ST1B .1000 .71960 5.36 10.70
+-3ERIC ST1C
+-1ROLA ST1A .6342 2.3507 3.02 20.27
+-2ROLB ST1B .1005 .72150 5.36 20.27
+-3ROLC ST1C
+-1DAVA ST1A .6641 2.3641 3.02 14.53
+-2DAVB ST1B .0998 .71990 5.36 14.53
+-3DAVC ST1C
+-1STTA HOMA .6129 1.9245 4.50 214.0
+-2STTB HOMB .0502 .59410 7.05 214.0
+-3STTC HOMC
+ ST3A STTA .3737
+ ST3B STTB .3737
+ ST3C STTC .3737
+ ST1A SWIA .0415
+ ST1B SWIB .0415
+ ST1C SWIC .0415
+ ST3A 96514. 1930.
+ ST3B 96514. 1930.
+ ST3C 96514. 1930.
+C ST3A 12.82
+C ST3B 12.82
+C ST3C 12.82
+C SWPA 37.70
+C SWPB 37.70
+C SWPC 37.70
+BLANK card ending all branch cards
+ SWIA SWPA .007940 1.0 1
+ SWIB SWPB .007940 1.0 1
+ SWIC SWPC .007940 1.0 1
+BLANK card ending all switch cards
+14SORA 93800. 60. 185. -1.0
+14SORB 93800. 60. 65. -1.0
+14SORC 93800. 60. -55. -1.0
+C SWPA |TERRA *SWIA *
+C SWPB |TERRA *SWIB *
+C SWPC |TERRA *SWIC *
+C ST3A |TERRA *TERRA *STTA *
+C ST3B |TERRA *TERRA *STTB *
+C ST3C |TERRA *TERRA *STTC *
+C < < Etc. (many more rows) > >
+BLANK card ending all source cards
+ ST3A ST3B ST3C HOMA HOMB HOMC SWPA SWPB SWPC
+C Total network loss P-loss by summing injections = 4.805638098099E+02
+C
+C Last gen: SORC 53801.469729728 93800. 23.911871905618 29.188614218823
+C -76836.46175431 -55.0000000 16.739103380547 34.9932955
+C
+C Step Time ST3A ST3B ST3C HOMA HOMB HOMC
+C SWPA
+C SWIB SWIC CHEN CHEN CHEN CHEN
+C SWPB SWPC CURR1 FLUX1 CURR2 FLUX2
+C
+C CHEN CHEN CHEN CHEN
+C CURR5 FLUX5 CURR6 FLUX6
+C
+C 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0
+C 100 .005 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0 0.0 0.0
+C 0.0 0.0 0.0 0.0
+C *** Close switch "SWIA " to "SWPA " after 7.95000000E-03 sec.
+C *** Close switch "SWIB " to "SWPB " after 7.95000000E-03 sec.
+C *** Close switch "SWIC " to "SWPC " after 7.95000000E-03 sec.
+C 200 .01 217387.84 -10992.36 -206395.4 310888.096 -111376.98 -199510.83
+C -104.63191 -2105.0079 2209.64051 .734405004 -104.63005 -.18043359
+C 34.108862 -.17539116 699.385843 -.45096469
+BLANK card ending selective node voltage output requests
+C 1000 .05 -155842.05 47154.6268 -24422.789 258598.902 172156.84 -81252.716
+C 2571.94767 -2427.6366 -1947.2216 .242401327 2597.62728 2.19565639
+C 1.17575901 2.19555992 325.890333 -1.8799098
+C maxima : 669374.836 515148.465 484746.844 .1044677E7 660808.946 731972.517
+C 3607.09709 3846.82291 5375.85965 1.84806576 3607.09698 2.51948617
+C 1360.93644 2.71806614 1676.35273 1.0164742
+C Times of max : .0413 .01425 .03845 .04145 .03025 .0386
+C .0428 .0369 .03965 .0133 .0428 .01685
+C .0165 .01685 .0408 .04075
+C minima : -571739.71 -410695.52 -617164.56 -648371.12 -532251.9 -900333.66
+C -1991.6408 -5018.5588 -5328.1211 -1.7469988 -1991.6406 -.60320685
+C -1205.0922 -.78031949 -1766.5889 -2.6833277
+C Times of min : .01605 .04025 .02785 .0454 .0185 .02775
+C .0232 .0408 .0433 .03805 .0232 .04275
+C .0428 .04275 .02955 .03
+ PRINTER PLOT
+C For a CALCOMP (vector) plot like Fig. MVI-1 on page 20 of the Ammendment to
+C the final report (Ammendment dated 23 May 1993), use this plot card:
+C 144 5. 0.0 50. ST3A ST3B ST3C High voltages Voltages, V
+ 144 2. 0.0 20. ST3A { Axis limits: (-5.717, 3.942)
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+BLANK
+
|