summaryrefslogtreecommitdiffstats
path: root/benchmarks/dcp9.dat
diff options
context:
space:
mode:
authorAngelo Rossi <angelo.rossi.homelab@gmail.com>2023-06-21 12:04:16 +0000
committerAngelo Rossi <angelo.rossi.homelab@gmail.com>2023-06-21 12:04:16 +0000
commitb18347ffc9db9641e215995edea1c04c363b2bdf (patch)
treef3908dc911399f1a21e17d950355ee56dc0919ee /benchmarks/dcp9.dat
Initial commit.
Diffstat (limited to 'benchmarks/dcp9.dat')
-rw-r--r--benchmarks/dcp9.dat60
1 files changed, 60 insertions, 0 deletions
diff --git a/benchmarks/dcp9.dat b/benchmarks/dcp9.dat
new file mode 100644
index 0000000..d11dd1d
--- /dev/null
+++ b/benchmarks/dcp9.dat
@@ -0,0 +1,60 @@
+BEGIN NEW DATA CASE
+C BENCHMARK DCPR-9
+C Like preceding case number 7, only with balanced 3-phase excitation here
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns)
+DIAGNOSTIC 0 9 9 9 9 9 0 9 9 9 9 9 9 3 9 9 9 9 9
+ .05 1.0 60. 60.
+ 1 1 1 1 1 -1
+ 2 -1
+ RECA .001 { Short the receiving end through R=1.E-3
+ RECB .001 { ohm resistors, so that lots of current
+ RECC .001 { will flow (no subtle effects here!).
+ 1SENDA RECA 1.0 1.0 1.E4
+ 2SENDB RECB 0.7 0.3 -2.E3 1.0 1.0 1.E4
+ 3SENDC RECC 0.7 0.3 -2.E3 0.7 0.3 -2.E3 1.0 1.0 1.E4
+BLANK card ending branch cards
+ GENA SENDA -1.0 9.0
+ GENB SENDB -1.0 9.0
+ GENC SENDC -1.0 9.0
+BLANK card ending switch cards
+14GENA 100. 1.0 0.0 -1.
+14GENB 100. 1.0 -120. -1.
+14GENC 100. 1.0 +120. -1.
+BLANK card ending source cards
+C Total network loss P-loss by summing injections = 4.975913322375E+04
+C Output for steady-state phasor switch currents.
+C Node-K Node-M I-real I-imag I-magn
+C GENA SENDA 0.33172755E+03 -0.12847657E+02 0.33197625E+03
+C GENB SENDB -0.17699017E+03 -0.28086066E+03 0.33197625E+03
+C GENC SENDC -0.15473738E+03 0.29370832E+03 0.33197625E+03
+C Last inject: GENC
+C Last inject: SENDC -50. 100. -154.737380025 331.97625355128
+C Last inject: 86.602540378444 120.000000 293.70831814053 117.7820691
+C Step Time RECC RECB RECA SENDC SENDB
+C
+C GENC
+C *** Phasor I(0) = 0.3317276E+03 Switch "GENA " to "SENDA " closed
+C *** Phasor I(0) = -0.1769902E+03 Switch "GENB " to "SENDB " closed
+C *** Phasor I(0) = -0.1547374E+03 Switch "GENC " to "SENDC " closed
+C 0 0.0 -.15472869 -.176998863 .3317275535 -50. -50.
+C -50.
+C 1 .05 -.237782502 -.081702388 .3194848903 -74.3144825 -20.7911691
+C -74.3144825
+ 1
+C 2 0.1 -.297802788 .0218130975 .2759896908 -91.3545458 10.45284633
+C -91.3545458
+C 20 1.0 -.154632329 -.177086923 .3317192528 -50. -50.
+C -50.
+C Variable max : .3285470726 .3312545968 .3317275535 99.45218954 99.45218954
+C 99.45218954
+C Times of max : .65 .35 0.0 .65 .35
+C .65
+C Variable min : -.328525683 -.331257201 -.331719199 -99.4521895 -99.4521895
+C -99.4521895
+C Times of min : .15 .85 0.5 .15 .85
+C .15
+ PRINTER PLOT { Axis limits : (-3.317, 3.317)
+ 143 .1 0.0 1.0 RECA { This receiving end voltage is nice & sinusoidal
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+BLANK