@@ -0,0 +1,519 @@
+BEGIN NEW DATA CASE
+C BENCHMARK DC-41
+C Test of Semlyen frequency-dependent simulation code using high-order
+C data from John Hauer (former "HAUER SETUP"). This is the John Day to
+C Lower Monumental fault test, just like DC-31 (2nd order Semlyen) and
+C DCNEW-4 (high-order Marti). Here, continuous transposition is assumed
+PRINTED NUMBER WIDTH, 12, 2, { Request maximum precision (for 9 output columns)
+ 20.E-6 20.E-3 60. 60.
+ 1 8 1 1 -1
+ 5 5 20 20 100 100
+ 0GENA BEGINA 14.
+ 0GENB BEGINBGENA BEGINA
+ 0GENC BEGINCGENA BEGINA
+C The following branch cards are from "HAUER SETUP" punch file:
+C #DATA FOR LINE SECTION 1: LENGTH = 0.1380000E+03
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 -0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 3.3636 .05215 4 1.602 19.25 50. 50.
+C 3.3636 .05215 4 1.602 20.75 50. 50.
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C
+C 27. 60. 1 138.
+C 27. 6.0 1 138. 7 20
+C
+-1BEGINAENDA 0.22547E-02 0.74884E-03 1 1 14 6 3
+ 0.67519497E+02 0.22868008E+03 0.00000000E+00 0.62996694E-03 0.60000000E+02 0
+ 0., 0.232728400E+03, 0.505695185E-01, 0., 0.618279420E+03, 0.748306243E-01
+ 0., 0.460330237E+04, 0.227732022E+00, 0., 0.873771583E+04,-0.587245219E-01
+ 0., 0.900430932E+04, 0.249999225E-01, 0., 0.159407707E+05, 0.975160389E+00
+ 0., 0.194752175E+05, 0.117242152E+00, 0., 0.366005345E+05, 0.548528443E+00
+ 0., 0.654818466E+05,-0.150033701E+01, 0., 0.212800153E+06, 0.120734101E+02
+ 0., 0.271680247E+06,-0.185580738E+05, 0., 0.273142633E+06, 0.342711488E+05
+ 0., 0.275102479E+06,-0.160808604E+05, 0., 0.287226841E+06, 0.356251978E+03
+ 0., 0.464830983E+03,-0.469956828E-03, 0., 0.243280470E+05, 0.123116414E-03
+ 0., 0.135508543E+05,-0.279583141E-03, 0., 0.166820988E+06, 0.206387276E-03
+ 0., 0.151012880E+06,-0.350762015E-03, 0., 0.304998812E+07,-0.622090423E-04
+-1BEGINBENDB 0.35258E-02 0.74313E-03 2 2 14 2 3
+ 0.40944359E+01 0.80845419E+02 0.00000000E+00 0.10069636E-02 0.60000000E+02 0
+ 0., 0.827674470E+03, 0.398806056E-01, 0., 0.130501996E+06, 0.508365787E+00
+ 0., 0.252780509E+06,-0.280985689E+00, 0., 0.260749831E+06, 0.360866589E+00
+ 0., 0.544371051E+06,-0.152645223E+01, 0., 0.696229069E+06, 0.773993647E+01
+ 0., 0.768161125E+06,-0.566855648E+01, 0., 0.415043368E+07,-0.224486177E+00
+ 0., 0.860106666E+07,-0.180297330E+02, 0., 0.104572655E+08, 0.286577225E+03
+ 0., 0.118008018E+08,-0.243527045E+05, 0., 0.119761142E+08, 0.200319291E+06
+ 0., 0.120018677E+08,-0.177347835E+06, 0., 0.125804003E+08, 0.111275201E+04
+ 0., 0.000000000E+00, 0.000000000E+00, 0., 0.000000000E+00, 0.000000000E+00
+-1BEGINCENDC 0.35258E-02 0.74313E-03 3 3 14 2 3
+ 0.40944359E+01 0.80845419E+02 0.00000000E+00 0.10069636E-02 0.60000000E+02 0
+ 0., 0.827674470E+03, 0.398806056E-01, 0., 0.130501996E+06, 0.508365787E+00
+ 0., 0.252780509E+06,-0.280985689E+00, 0., 0.260749831E+06, 0.360866589E+00
+ 0., 0.544371051E+06,-0.152645223E+01, 0., 0.696229069E+06, 0.773993647E+01
+ 0., 0.768161125E+06,-0.566855648E+01, 0., 0.415043368E+07,-0.224486177E+00
+ 0., 0.860106666E+07,-0.180297330E+02, 0., 0.104572655E+08, 0.286577225E+03
+ 0., 0.118008018E+08,-0.243527045E+05, 0., 0.119761142E+08, 0.200319291E+06
+ 0., 0.120018677E+08,-0.177347835E+06, 0., 0.125804003E+08, 0.111275201E+04
+ 0., 0.000000000E+00, 0.000000000E+00, 0., 0.000000000E+00, 0.000000000E+00
+C ** TX MATRICES: FTX= 0.00000E+00
+ 0.57735026919E+00, 0., 0.70710678119E+00, 0., 0.40824829046E+00, 0.
+ 0.57735026919E+00, 0.,-0.70710678119E+00, 0., 0.40824829046E+00, 0.
+ 0.57735026919E+00, 0., 0.00000000000E+00, 0.,-0.81649658093E+00, 0.
+ 0.57735026919E+00, 0., 0.70710678119E+00, 0., 0.40824829046E+00, 0.
+ 0.57735026919E+00, 0.,-0.70710678119E+00, 0., 0.40824829046E+00, 0.
+ 0.57735026919E+00, 0., 0.00000000000E+00, 0.,-0.81649658093E+00, 0.
+C End of branch cards from "HAUER SETUP" punch file.
+C Modification on 15 February 1999: "1" punch was added to column 80 of the
+C 3rd and final phase of preceding Semlyen line. Output is identical.
+ RRR 10. { Resistor connects ANALYTIC source to ground
+BLANK card ending branch cards
+ ENDA .00413 1.0
+BLANK card ending switch cards (just the fault switch, here)
+14GENA 428. 60. -90.0 -1.
+14GENB 428. 60. -210.0 -1.
+14GENC 428. 60. 30.0 -1.
+C 27 October 2003, add the same new user-supplied source as featured in 7th
+C subcase of BENCHMARK DC-5. But here there is continuation into dT loop.
+C Show that phasor solution is as expected and no special problem results.
+C The only peculiarity is the need to key the frequency in columns 21-30. If
+C this is not done, the default value of 1 Hz will result. A final change is
+C the request for node voltage outputs. This was "1", which if left, would
+C add an output column that is identically zero for step 1 onward. This is
+C not interesting, so suppress this output by a switch to selective outputs.
+C Node V? Request> -Name-
+14RRR -1 60. ANALYTIC HYPERB
+C Preceding is defined as follows: Real part = 100. * Pi / Omega
+C Imaginary part = ( Real part + 1.0 ) / 2
+C So at 60 Hz, phasor = 5/6 + j 11/12
+BLANK card ending source cards
+C Total network loss P-loss by summing injections = 4.183407681766E-01
+C Last inject: GENC 370.65887281974 428. -.2242277044615 .44958452206004
+C Last inject: 214. 30.0000000 .38967701886034 119.9169563
+C Step Time ENDC ENDB ENDA BEGINC BEGINB
+C
+C 0 0.0 392.438957 -391.47028 -.96868127 376.114351 -376.10523
+C 1 .2E-4 393.416785 -390.51658 -2.9002095 373.022592 -371.61198
+C 2 .4E-4 391.718167 -392.23056 .512394524 371.605264 -374.09974
+ ENDC ENDB ENDA BEGINCBEGINBBEGINAGENA GENB GENC
+BLANK card ending request for node voltage outputs
+C Final step begins: 1000 .02 -224.41449 -471.83274 0.0 -91.175647
+C Final step ..... : -323.88611 368.601969 407.052189 -318.06599 -88.986204
+C Variable maxima : 586.693087 525.250186 448.452866 438.684658 447.869952
+C Times of maxima : .01492 .01068 .00414 .0154 .00984
+ PRINTER PLOT
+ 144 2. 0.0 20. ENDB ENDA { Axis limits: (-5.167, 5.239)
+ 144 1. 0.0 6.0 ENDB ENDA { Axis limits: (-4.555, 4.485)
+ CALCOMP PLOT
+ 144 2. 0.0 20. ENDB ENDA
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 2nd of 7 subcases is related to preceeding. The same 138-mile section of
+C 500-kV line is involved, but without frequency dependence for simplicity.
+C Rather than a fault to ground, the source of phase "a" is ended at 1 msec
+C (same effect, only at sending end rather than receiving end). Nice
+C transients are documented by a printer plot. This establishes the
+C reference for the radical new solution of the following 3rd subcase.
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (if 8 output columns)
+ .000050 .005 60. 60.
+ 1 1 1 3 1 -1 2
+ 5 5 20 20 100 100
+ JDGA JDA 15. { 1st of 3 branches in series with one
+ JDGB JDB 15. { section of K.C. Lee line. This is
+ JDGC JDC 15. { an approximation to source impedance
+C The following 3-phase, constant-parameter branch cards are produced by the
+C 2nd subcase of DC-59. For simplicity, the cards are inserted inside this
+C data file. Equally well, $INCLUDE or $INSERT on disk file dc59b.pch
+C could be used:
+$VINTAGE, 1 { Beginning of cards punched by DC-59b
+-1JDA LMA 3.01533E-01 6.91823E+02 1.19371E+05 1.38000E+02 1
+-2JDB LMB { See col 80 } 2.80266E-02 2.83599E+02 1.82176E+05 1.38000E+02 1 0
+-3JDC LMC
+$VINTAGE, 0 { last of cards punched by DC-59b
+C Modification on 15 February 1999: "3" punch was added to column 80 of the
+C 2nd phase of preceding distributed line. Output is identical except for
+C the interpreted data line itself. Because of the otherwise-unused in-line
+C comment, the "3" will be seen (unlike preceding subcase or DCNEW-4).
+ LMA 1000. { Resistive load at far end of 1st of 6 phases
+ LMB LMA { 2nd of 6 phases is terminated by the same R
+ LMC LMA { Etc. for phases 3 through 6. It is balanced
+BLANK card ending branch cards
+BLANK card ending switch cards
+14JDGA 303000. 60. 0. -1. .001
+14JDGB 303000. 60. -120. -1.
+14JDGC 303000. 60. 120. -1.
+BLANK card ending source cards
+ JDGA LMA JDGB LMB JDGC LMC
+BLANK card ending node names for selective voltage output
+ PRINTER PLOT
+ 144 1. 0.0 5.0 LMA LMB LMC
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 3rd of 7 subcases should produce identically the same solution as the
+C preceding subcase. Added 29 January 1999, this illustrates the new
+C "TO SUPPORTING PROGRAM" to derive line constants of the 138-mile line
+C section as were used in the 2nd subcase of DC-59. As should be explained
+C in the April, 1999, newsletter, this new in-line execution of supporting
+C programs first was envisioned by Prof. Juan A. Martinez Velasco of the
+C University of Catalunya in Barcelona, Spain.
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (if 8 output columns)
+ .000050 .005 60. 60.
+ 1 1 1 3 1 -1 2
+ 5 5 20 20 100 100
+ JDGA JDA 15. { 1st of 3 branches in series with one
+ JDGB JDB 15. { section of K.C. Lee line. This is
+ JDGC JDC 15. { an approximation to source impedance
+C Add /OUTPUT anywhere on right of following request to produce output of
+C the supporting program. Without this, all output will be suppressed.
+< TO SUPPORTING PROGRAM (NEXT) > { Request for a jump to a supporting program
+C The following data, through the blank card, is from 2nd subcase of DCNEW-3.
+LINE CONSTANTS
+BRANCH JDA LMA JDB LMB JDC LMC
+C LINE CONSTANTS DATA FOR JOHN DAY TO LOWER MONUMENTAL 500-KV LINE.
+ 1.3636 .05215 4 1.602 -20.75 50. 50.
+ 1.3636 .05215 4 1.602 -19.25 50. 50.
+ 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+ 2.3636 .05215 4 1.602 0.75 77.5 77.5
+ 3.3636 .05215 4 1.602 19.25 50. 50.
+ 3.3636 .05215 4 1.602 20.75 50. 50.
+ 0.5 2.61 4 0.386 -12.9 98.5 98.5
+ 0.5 2.61 4 0.386 12.9 98.5 98.5
+BLANK CARD ENDING CONDUCTOR CARDS OF "LINE CONSTANTS" CASE
+100. 60.00 1 11 1 138. 1
+BLANK CARD ENDING FREQUENCY CARDS OF "LINE CONSTANTS" CASE
+$PUNCH, dc41c.pch ! { Output the just-created branch cards to a disk file
+BLANK card ending LINE CONSTANTS data cases { Last of supporting program data
+$CLOSE, UNIT=7 STATUS=KEEP { Disconnect file containing KC Lee branch cards
+$INSERT, dc41c.pch, { Dynamic connection of disk file created 3 lines above
+ LMA 1000. { Resistive load at far end of 1st of 3 phases
+ LMB LMA { 2nd of 3 phases is terminated by the same R
+ LMC LMA
+BLANK card ending branch cards
+BLANK card ending switch cards
+14JDGA 303000. 60. 0. -1. .001
+14JDGB 303000. 60. -120. -1.
+14JDGC 303000. 60. 120. -1.
+BLANK card ending source cards
+ JDGA LMA JDGB LMB JDGC LMC
+BLANK card ending node names for selective voltage output
+ PRINTER PLOT
+ 144 1. 0.0 5.0 LMA LMB LMC
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 4th of 7 subcases illustrates selective branch current output for 2-phase
+C Semlyen line. This was added 11 December 2000. Branch cards for the
+C 2-phase line are as created by the 3rd subcase of DC-29. The network is
+C totally artificial since it represents 2 of the 3 phases of a 500-kV line
+C The new "Derive [Ti] from [Tv]" request also is illustrated (see the
+C April, 2001, newsletter). Only a single time step is taken --- enough
+C to verify correct and consistent output.
+PRINTED NUMBER WIDTH, 12, 2, { Request maximum precision (for 9 output columns)
+ 20.E-6 20.E-6 60. 60.
+ 1 8 0 1 0
+ 0GENA BEGINA 14. 1
+ 0GENB BEGINBGENA BEGINA 1
+C 0GENC BEGINCGENA BEGINA 1
+C <++++++> Cards punched by support routine on 11-Nov-18 11.00.00 <++++++>
+C SEMLYEN SETUP
+C $ERASE
+C BRANCH JDA LMA JDB LMB
+C TOLERANCES 10 5000. { Illustration only; value of FMED actually unchang
+C 200 150 10 230 1 7 7777 0 { Semlyen miscellaneous da
+C LINE CONSTANTS
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C BLANK card ending conductor cards within "LINE CONSTANTS" data
+C 27. 5000. 138. { Transient frequen
+C 27. 60.00 138. { Phasor solution frequen
+C 27. 6.00 138. 6 20 { log loopi
+C BLANK card ending frequency cards of "LINE CONSTANTS" data
+C BLANK card ending "LINE CONSTANTS" data cases
+C L= 138.0 miles, rho= 27.0, ss freq= 60.00, NSS=0, KFIT=10, KPS=2, KYC=30
+-1BEGINAENDA 3.81668E-03 7.63488E-04 1 1 2 2 2 0
+ 1.90862630E+01 1.15862674E+02-1.30872176E-04 9.74276128E-04 6.00000000E+01
+ 0.00000E+00 2.24216E+04 7.46515E-01 0.00000E+00 2.38744E+03 2.53485E-01
+ 0.00000E+00 1.23894E+05-4.11230E-04 0.00000E+00 4.80703E+02-8.78400E-04
+-1BEGINBENDB 4.86411E-03 7.40372E-04 2 2 2 2 2 1
+ 1.59520125E+00 6.09143723E+01-2.53812008E-05 1.35128690E-03 6.00000000E+01
+ 0.00000E+00 4.07374E+05 9.54406E-01 0.00000E+00 2.40730E+03 4.55945E-02
+ 0.00000E+00 2.43743E+03-1.39286E-04 0.00000E+00 8.77099E+01-3.84337E-04
+NO IMAGINARY PART:
+ 1.0000000000000002E+00 -5.9460940886557245E-01
+ 6.9285574025886665E-01 1.0000000000000000E+00
+ 7.0805987238797719E-01 -4.9148565643201919E-01
+ 4.2216590194629711E-01 7.0805987238797719E-01
+YES, IMAGINARY PART: { Do-nothing request for return to default mode of complex
+Derive [Ti] from [Tv] { Do it. I.e., preceding [Ti] is not used.
+C Relative order of the preceding two declarations is arbitrary. Either is
+C voluntary, and either can come first, immediately after the matrix.
+BLANK card ending branch cards
+ ENDA .00413 1.0
+BLANK card ending switch cards (just the fault switch, here)
+14GENA 428. 60. -90.0 -1.
+14GENB 428. 60. -210.0 -1.
+C 14GENC 428. 60. 30.0 -1.
+BLANK card ending source cards
+ BEGINAENDA
+C First 2 output variables are electric-network voltage differences (upper voltage minus lower voltage);
+C Next 3 output variables are branch currents (flowing from the upper node to the lower node);
+C Step Time BEGINA ENDA GENA GENB BEGINB
+C BEGINA BEGINB ENDB
+C 0 0.0 1.31770789 -1.9263914 .416683394 -.25532666 -.25532666
+C 1 .2E-4 4.58886445 1.51135697 .415961844 -.2528793 -.2528793
+BLANK card ending node voltage outputs
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 5th of 7 subcases illustrates selective branch current output for 2-phase
+C Semlyen line. This was added 11 December 2000. It is identical to the
+C preceding subcase except that "Derive [Ti] from [Tv]" is not being used
+C to illustrate how the answer changes. Note inconsistent current at time
+C zero but consistent current for step 1.
+PRINTED NUMBER WIDTH, 12, 2, { Request maximum precision (for 9 output columns)
+ 20.E-6 20.E-6 60. 60.
+ 1 8 0 1 0
+ 0GENA BEGINA 14. 1
+ 0GENB BEGINBGENA BEGINA 1
+C 0GENC BEGINCGENA BEGINA 1
+C <++++++> Cards punched by support routine on 11-Nov-18 11.00.00 <++++++>
+C SEMLYEN SETUP
+C $ERASE
+C BRANCH JDA LMA JDB LMB
+C TOLERANCES 10 5000. { Illustration only; value of FMED actually unchang
+C 200 150 10 230 1 7 7777 0 { Semlyen miscellaneous da
+C LINE CONSTANTS
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C BLANK card ending conductor cards within "LINE CONSTANTS" data
+C 27. 5000. 138. { Transient frequen
+C 27. 60.00 138. { Phasor solution frequen
+C 27. 6.00 138. 6 20 { log loopi
+C BLANK card ending frequency cards of "LINE CONSTANTS" data
+C BLANK card ending "LINE CONSTANTS" data cases
+C L= 138.0 miles, rho= 27.0, ss freq= 60.00, NSS=0, KFIT=10, KPS=2, KYC=30
+-1BEGINAENDA 3.81668E-03 7.63488E-04 1 1 2 2 2 0
+ 1.90862630E+01 1.15862674E+02-1.30872176E-04 9.74276128E-04 6.00000000E+01
+ 0.00000E+00 2.24216E+04 7.46515E-01 0.00000E+00 2.38744E+03 2.53485E-01
+ 0.00000E+00 1.23894E+05-4.11230E-04 0.00000E+00 4.80703E+02-8.78400E-04
+-1BEGINBENDB 4.86411E-03 7.40372E-04 2 2 2 2 2 1
+ 1.59520125E+00 6.09143723E+01-2.53812008E-05 1.35128690E-03 6.00000000E+01
+ 0.00000E+00 4.07374E+05 9.54406E-01 0.00000E+00 2.40730E+03 4.55945E-02
+ 0.00000E+00 2.43743E+03-1.39286E-04 0.00000E+00 8.77099E+01-3.84337E-04
+NO IMAGINARY PART:
+ 1.0000000000000002E+00 -5.9460940886557245E-01
+ 6.9285574025886665E-01 1.0000000000000000E+00
+ 7.0805987238797719E-01 -4.9148565643201919E-01
+ 4.2216590194629711E-01 7.0805987238797719E-01
+YES, IMAGINARY PART:
+C Derive [Ti] from [Tv] ---- disable this declaration of preceding subcase
+BLANK card ending branch cards
+ ENDA .00413 1.0
+BLANK card ending switch cards (just the fault switch, here)
+14GENA 428. 60. -90.0 -1.
+14GENB 428. 60. -210.0 -1.
+BLANK card ending source cards
+ BEGINAENDA
+C First 2 output variables are electric-network voltage differences (upper voltage minus lower voltage);
+C Next 3 output variables are branch currents (flowing from the upper node to the lower node);
+C Step Time BEGINA ENDA GENA GENB BEGINB
+C BEGINA BEGINB ENDB
+C 0 0.0 1.3173033 -1.93736 .417090545 -.25540157 -.25506625
+C 1 .2E-4 4.46159339 1.51090777 .416403376 -.25292062 -.25292062
+BLANK card ending node voltage outputs
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 6th of 7 subcases illustrates selective branch current output for 3-phase
+C Semlyen line. This was added 11 December 2000. There is no current
+C output for phase "a" whereas there is output for phases "b" and "c".
+C Also, the new "Derive [Ti] from [Tv]" is being used.
+PRINTED NUMBER WIDTH, 12, 2, { Request maximum precision (for 9 output columns)
+ 20.E-6 20.E-6 60. 60.
+ 1 8 0 1 0
+ 0GENA BEGINA 14. 1
+ 0GENB BEGINBGENA BEGINA 1
+ 0GENC BEGINCGENA BEGINA 1
+C L= 138.0MILES, RHO= 27.0, SS FREQ= 60.00, NSS=0, KFIT= 0, KPS=2, KYC=10
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 3.3636 .05215 4 1.602 19.25 50. 50.
+C 3.3636 .05215 4 1.602 20.75 50. 50.
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C
+C 27. 5000. 1 138.
+C 27. 60.00 1 138.
+C 27. 6.00 1 138. 6 20
+C
+-1BEGINAENDA 0.55456E-02 0.77998E-03 1 1 2 2 3 0
+ 0.14938602E+02 0.90516313E+02-0.16261865E-03 0.14500324E-02 0.60000000E+02
+ 0.00000E+00 0.15161E+05 0.75119E+00 0.00000E+00 0.17105E+04 0.24881E+00
+ 0.00000E+00 0.59584E+03-0.11954E-02 0.00000E+00 0.39933E+05-0.74162E-03
+-1BEGINBENDB 0.74392E-02 0.74149E-03 2 2 2 2 3 1
+ 0.83801231E+00 0.38634735E+02-0.44536501E-04 0.20637999E-02 0.60000000E+02
+ 0.00000E+00 0.26608E+06 0.83767E+00 0.00000E+00 0.35627E+05 0.16233E+00
+ 0.00000E+00 0.13630E+03-0.49171E-03 0.00000E+00 0.32940E+05-0.75349E-04
+-1BEGINCENDC 0.42823E-02 0.74017E-03 3 3 2 2 3 1
+ 0.26535168E+01 0.67894100E+02-0.45225808E-04 0.11682248E-02 0.60000000E+02
+ 0.00000E+00 0.61698E+06 0.90903E+00 0.00000E+00 0.15239E+05 0.90969E-01
+ 0.00000E+00 0.25667E+03-0.34465E-03 0.00000E+00 0.11831E+05-0.28233E-04
+ 0.10000E+01 0.00000E+00 0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.71114E+00 0.00000E+00-0.41983E-15 0.00000E+00 0.10000E+01 0.00000E+00
+ 0.10000E+01 0.00000E+00-0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00 0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+ 0.22471E+00 0.00000E+00-0.27373E-15 0.00000E+00 0.84054E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00-0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+Derive [Ti] from [Tv]
+BLANK card ending branch cards
+ ENDA .00413 1.0
+C ENDA -1.0 1.0
+BLANK card ending switch cards (just the fault switch, here)
+14GENA 428. 60. -90.0 -1.
+14GENB 428. 60. -90.0 -1.
+14GENC 428. 60. -90.0 -1.
+BLANK card ending source cards
+ BEGINAENDA
+C First 2 output variables are electric-network voltage differences (upper voltage minus lower voltage);
+C Next 5 output variables are branch currents (flowing from the upper node to the lower node);
+C Step Time BEGINA ENDA GENA GENB GENC BEGINB BEGINC
+C BEGINA BEGINB BEGINC ENDB ENDC
+C 0 0.0 .433757964 -1.3235974 .255657761 .262352453 .255657761 .262352453 .255657761
+C 1 .2E-4 3.68776594 2.16693321 .255416888 .262183584 .255416888 .262183584 .255416888
+BLANK card ending node voltage outputs
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+C 7th of 7 subcases illustrates selective branch current output for 3-phase
+C Semlyen line. This was added 11 December 2000. It is identical to the
+C preceding subcase except that "Derive [Ti] from [Tv]" is not being used
+C to illustrate how the answer changes. Note inconsistent current at time
+C zero but correct current for step 1.
+PRINTED NUMBER WIDTH, 12, 2, { Request maximum precision (for 9 output columns)
+ 20.E-6 20.E-6 60. 60.
+ 1 8 0 1 0
+ 0GENA BEGINA 14. 1
+ 0GENB BEGINBGENA BEGINA 1
+ 0GENC BEGINCGENA BEGINA 1
+C L= 138.0MILES, RHO= 27.0, SS FREQ= 60.00, NSS=0, KFIT= 0, KPS=2, KYC=10
+C 1.3636 .05215 4 1.602 -20.75 50. 50.
+C 1.3636 .05215 4 1.602 -19.25 50. 50.
+C 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+C 2.3636 .05215 4 1.602 0.75 77.5 77.5
+C 3.3636 .05215 4 1.602 19.25 50. 50.
+C 3.3636 .05215 4 1.602 20.75 50. 50.
+C 0.5 2.61 4 0.386 -12.9 98.5 98.5
+C 0.5 2.61 4 0.386 12.9 98.5 98.5
+C
+C 27. 5000. 1 138.
+C 27. 60.00 1 138.
+C 27. 6.00 1 138. 6 20
+C
+-1BEGINAENDA 0.55456E-02 0.77998E-03 1 1 2 2 3 0
+ 0.14938602E+02 0.90516313E+02-0.16261865E-03 0.14500324E-02 0.60000000E+02
+ 0.00000E+00 0.15161E+05 0.75119E+00 0.00000E+00 0.17105E+04 0.24881E+00
+ 0.00000E+00 0.59584E+03-0.11954E-02 0.00000E+00 0.39933E+05-0.74162E-03
+-1BEGINBENDB 0.74392E-02 0.74149E-03 2 2 2 2 3 1
+ 0.83801231E+00 0.38634735E+02-0.44536501E-04 0.20637999E-02 0.60000000E+02
+ 0.00000E+00 0.26608E+06 0.83767E+00 0.00000E+00 0.35627E+05 0.16233E+00
+ 0.00000E+00 0.13630E+03-0.49171E-03 0.00000E+00 0.32940E+05-0.75349E-04
+-1BEGINCENDC 0.42823E-02 0.74017E-03 3 3 2 2 3 1
+ 0.26535168E+01 0.67894100E+02-0.45225808E-04 0.11682248E-02 0.60000000E+02
+ 0.00000E+00 0.61698E+06 0.90903E+00 0.00000E+00 0.15239E+05 0.90969E-01
+ 0.00000E+00 0.25667E+03-0.34465E-03 0.00000E+00 0.11831E+05-0.28233E-04
+ 0.10000E+01 0.00000E+00 0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.71114E+00 0.00000E+00-0.41983E-15 0.00000E+00 0.10000E+01 0.00000E+00
+ 0.10000E+01 0.00000E+00-0.10000E+01 0.00000E+00-0.26698E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00 0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+ 0.22471E+00 0.00000E+00-0.27373E-15 0.00000E+00 0.84054E+00 0.00000E+00
+ 0.42027E+00 0.00000E+00-0.50000E+00 0.00000E+00-0.29908E+00 0.00000E+00
+C Derive [Ti] from [Tv] ---- disable this declaration of preceding subcase
+BLANK card ending branch cards
+ ENDA .00413 1.0
+BLANK card ending switch cards (just the fault switch, here)
+14GENA 428. 60. -90.0 -1.
+14GENB 428. 60. -90.0 -1.
+14GENC 428. 60. -90.0 -1.
+BLANK card ending source cards
+ BEGINAENDA
+C First 2 output variables are electric-network voltage differences (upper voltage minus lower voltage);
+C Next 5 output variables are branch currents (flowing from the upper node to the lower node);
+C Step Time BEGINA ENDA GENA GENB GENC BEGINB BEGINC
+C BEGINA BEGINB BEGINC ENDB ENDC
+C 0 0.0 .434025265 -1.3246378 .255853054 .262494222 .255853054 .262738399 .255858717
+C 1 .2E-4 3.66889251 2.16376453 .255617191 .262340836 .255617191 .262340836 .255617191
+BLANK card ending node voltage outputs
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+$DISABLE { Begin discard of 4th subcase, which takes too long to execute
+C 8th of 7 subcases will produce a solution comparable to the 3rd, but
+C here constant-parameter K.C. Lee modeling of the line is replaced by
+C frequency-dependent JMarti modeling. This illustrates a more complex
+C in-line execution. On the other hand, JMARTI SETUP is relatively slow
+C to execute. That is why this 8th subcase will not be executed each time
+C the set of standard test cases is verified.
+PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (if 8 output columns)
+ .000050 .005 60. 60.
+ 1 1 1 3 1 -1 2
+ 5 5 20 20 100 100
+ JDGA JDA 15. { 1st of 3 branches in series with one
+ JDGB JDB 15. { circuit of the Marti line. This is
+ JDGC JDC 15. { an approximation to source impedance
+C Add /OUTPUT anywhere on right of following request to produce output of
+C the supporting program. Without this, all output will be suppressed.
+< TO SUPPORTING PROGRAM (NEXT) > { Request for jump to supporting programs
+C The following data, through the blank card, is from 2nd subcase of DCNEW-3.
+JMARTI SETUP, 1.0, { Note use of PDT0 = 1 to allow reduction of order
+$ERASE
+BRANCH JDA LMA JDB LMB JDC LMC
+LINE CONSTANTS
+C LINE CONSTANTS DATA FOR JOHN DAY TO LOWER MONUMENTAL 500-KV LINE.
+TRANSPOSED
+ 1.3636 .05215 4 1.602 -20.75 50. 50.
+ 1.3636 .05215 4 1.602 -19.25 50. 50.
+ 2.3636 .05215 4 1.602 - 0.75 77.5 77.5
+ 2.3636 .05215 4 1.602 0.75 77.5 77.5
+ 3.3636 .05215 4 1.602 19.25 50. 50.
+ 3.3636 .05215 4 1.602 20.75 50. 50.
+ 0.5 2.61 4 0.386 -12.9 98.5 98.5
+ 0.5 2.61 4 0.386 12.9 98.5 98.5
+BLANK CARD ENDING CONDUCTOR CARDS OF &LINE CONSTANTS& CASE
+100. 5000.0 1 138. 1 1
+100. 60.00 1 138. 1 1
+100. .01 1 138. 1 9 10 1
+BLANK CARD ENDING FREQUENCY CARDS OF "LINE CONSTANTS" CASE
+BLANK CARD ENDING "LINE CONSTANTS" CASES
+C 345678901234567890123456789012345678901234567890123456789012345678901234567890
+C SELECT +3 -3
+ 1 .48D-7
+ .30 30 0 1 1 1 0
+ .30 30 0 1 1 1 0 .0
+$PUNCH, dc41d.pch !
+BLANK card ending JMARTI SETUP data cases { Last of supporting program data
+$CLOSE, UNIT=7 STATUS=KEEP { Disconnect file containing JMarti branch cards
+$INSERT, dc41d.pch, { Dynamic connection of disk file created 3 lines above
+ LMA 1000. { Resistive load at far end of 1st of 3 phases
+ LMB LMA { 2nd of 3 phases is terminated by the same R
+ LMC LMA
+BLANK card ending branch cards
+BLANK card ending switch cards
+14JDGA 303000. 60. 0. -1. .001
+14JDGB 303000. 60. -120. -1.
+14JDGC 303000. 60. 120. -1.
+BLANK card ending source cards
+ JDGA LMA JDGB LMB JDGC LMC
+BLANK card ending node names for selective voltage output
+ PRINTER PLOT
+ 144 1. 0.0 5.0 LMA LMB LMC
+BLANK card ending plot cards
+BEGIN NEW DATA CASE
+$ENABLE { End discard of 4th subcase, which takes too long to execute
+BLANK
+