diff --git a/benchmarks/dc34.dat b/benchmarks/dc34.dat new file mode 100644 index 0000000..c2b6504 --- /dev/null +++ b/benchmarks/dc34.dat @@ -0,0 +1,194 @@ +BEGIN NEW DATA CASE
+C BENCHMARK DC-34
+C Test of U.M. operating as a 3-phase synchronous machine. Data is in
+C per unit. Although there is a phasor solution, manual initial conditions
+C in fact define all state variables, so the answers would be identical if
+C the negative (-1.0) starting times of the sources (T-start of cols. 61-70)
+C were erased (made blank --- or zero). For automatic initialization of
+C the same problem, see the second subcase (not normally executed). For a
+C case of automatic initialization using data in physical units, see DCNEW-2
+POWER FREQUENCY, 60.0, { Europeans need this (LEC letter dated 6 Jan 89, page 2)
+ .001 .500
+ 1 1 0 00 1 -1
+ 5 5 20 20 100 100
+ 0 BUS-F0 1.0
+ 0 BUS-A0 1.0
+ 0 BUS-B0 1.0
+ 0 BUS-C0 1.0
+ 0BUS-A1BUS-A0 0.02 1.0610 1
+ 0BUS-B1BUS-B0BUS-A1BUS-A0 1
+ 0BUS-C1BUS-C0BUS-A1BUS-A0 1
+ 0BUS-M1 2.00E6 1
+ 0BUS-M0 2.00E6 1
+ 0BUS-M0BUS-M1 1. 1
+BLANK card ends the last branch card
+BLANK card ends (in this case nonexistent) switch cards
+11BUS-F0 0.002091 { 18 Oct 90, remove ineffective T-start = -1.0 from card
+11BUS-M0-1 1.02
+11BUS-M0-1 -.4 .019500
+14BUS-A0 1.41421356 60.0 0.0 -1.0
+14BUS-B0 1.41421356 60.0 -120.0 -1.0
+14BUS-C0 1.41421356 60.0 120.0 -1.0
+C Note, the 3 following alternatives to the 3 preceding source cards would be
+C used if the user wanted to omit the unnecessary phasor solution:
+C 14BUS-A0 1.41421356 60.0 0.0
+C 14BUS-B0 1.41421356 60.0 -120.0
+C 14BUS-C0 1.41421356 60.0 120.0
+19 UM { Beginning of U.M. data (Type-19 source)
+1
+BLANK card ending class-1 U.M. data
+ 1 2 1111BUS-M1 1 1786.98 { 1st card of U.M. machine table
+1.0 1.550 0 0.3 1.5 1.0
+0.93787 1.490 0
+0.0 0.0 BUS-A1 1 1.3860 { 1st card of coil table
+0.001096 0.150 BUS-B1 1 -0.95877
+0.001096 0.150 BUS-C1 1 -0.42721
+0.00074 0.101 BUS-F0 1 -2.826
+0.0131 0.055 1
+0.0540 0.036 1
+BLANK card ending all U.M. data
+BLANK card ending EMTP source cards
+C Total network loss P-loss by summing injections = 2.999999989932E+00
+ 2BUS-A1 1.56413 { First of many initial condition cards for the
+ 2BUS-B1 -0.30745 { electric network. Since the U.M. is not a
+ 2BUS-C1 -1.25677 { part of the phasor solution (see DCNEW-1 for
+ 2BUS-A0 1.41421356 { such a more modern problem), synchronous
+ 2BUS-B0 -0.70710678 { operation can begin smoothly only if the
+ 2BUS-C0 -0.70710678 { initially conditions are manually applied.
+ 2BUS-F0 0.002091
+ 2BUS-M0 1.0
+ 2BUS-M1 1.0 { Final card of node voltage initial conditions
+ 3BUS-A1BUS-A0 1.38494 { 1st card of branch current initial conditions
+ 3BUS-B1BUS-B0 -0.95793
+ 3BUS-C1BUS-C0 -0.42701
+ 3 BUS-A0 -1.41421356
+ 3 BUS-B0 +0.70710678
+ 3 BUS-C0 +0.70710678
+ 3 BUS-F0 -0.002091
+ 3BUS-M0BUS-M1 +1.01
+ 3BUS-M0 +1.0
+ 3BUS-M1 +1.0 { Last card of branch current init. condit.
+ BUS-A1BUS-B1BUS-C1BUS-M1BUS-M0 { Request for selective node voltage output
+C Step Time BUS-A1 BUS-B1 BUS-C1 BUS-M1 BUS-M0 BUS-A1
+C BUS-A0
+C
+C BUS-M0 UM-1 UM-1 UM-1 UM-1 UM-1
+C BUS-M1 TQGEN OMEGM THETAM IPA IPB
+C 0 0.0 1.56413 -.30745 -1.25677 1.0 1.0 1.38494
+C 1.01 1.00124132 1.0 .93787 1.386 -.95877
+C 1 .001 1.25370608 .317284401 -1.5709433 1.00000302 1.0000025 1.40049668
+C 1.00999974 .997905631 1.0 .93787 1.40049668 -.50888659
+BLANK card ending the specification of output variables
+C Last step: 500 0.5 1.62762984 -.45832224 -1.1269996 1.00472639 1.00854631
+C Last step: .570740608 .701421892 1.00469204 .660491474 .974954484 -.86183035
+C maxima : 1.65791637 1.66126439 1.66752483 1.00779145 1.00854631 1.41537866
+C maxima : 1.01 1.0019948 1.00877611 .93787 1.41537866 1.40559809
+C Times of max : .466 .038 .494 .442 0.5 .034
+C Times of max : 0.0 .015 .439 .063 .034 .056
+C minima : -1.6665177 -1.6618744 -1.662372 .989230544 .990404468 -1.4043962
+C .322011281 .29918812 .988252614 .361026487 -1.4043962 -1.4122326
+C Times of min : .491 .063 .469 .158 .217 .059
+C .296 .346 .159 .358 .059 .031
+ PRINTER PLOT
+ 193 .1 0.0 1.0 BUS-M1BUS-M0 { Plot limits: (-1.010, 0.000)
+ 193 .1 0.0 1.0 UM-1 THETAM { Plot limits: (0.000, 9.379)
+BLANK card ending all plot cards
+BEGIN NEW DATA CASE
+BLANK { Note this extra blank will terminate execution, to avoid 2nd subcase
+C 2nd of 2 data subcases is a modification of the first that illustrates
+C correction of a U.M. bug by Yin Yuexin as explained in his September,
+C 1990, article in EMTP News. Automatic initialization of this data case
+C gave the wrong answers (although it did run) prior to correction of the
+C UTPF around 23 October 1990. Now, answers are close (most variables
+C differ by about 1% on the final time step). Printout of the final phasor
+C solution has deliberately been omitted, so those wanting to verify this
+C computation can observe only the total network loss (see comments below).
+POWER FREQUENCY, 60.
+ 0.0010 0.500
+ 1 1 1 0 1 -1
+ 5 5 20 20 100 100
+C --------- EMTP CONNECTIVITY
+ 0 BUS-A0 1.0
+ 0 BUS-B0 1.0
+ 0 BUS-C0 1.0
+C --------- TRANSMISSION LINES
+ 0BUS-A1BUS-A0 0.02 1.0610 1
+ 0BUS-B1BUS-B0BUS-A1BUS-A0 1
+ 0BUS-C1BUS-C0BUS-A1BUS-A0 1
+C --------- EMTP CONNECTIVITY REQUIREMENT
+ 0 BUS-F0 1.0
+ 0BUS-F0BUS-FS 1.0E-5
+C --------- MECH NETWORK
+ 0BUS-M1 2.00E6 1
+ 0BUS-M0 2.00E6 1
+ 0BUS-M0BUS-M1 1. 1
+BLANK card ends the last branch card
+BLANK card ends (in this case nonexistent) switch cards
+14BUS-A0 1.41421356 60 0.0 -1.0
+14BUS-B0 1.41421356 60 -120.0 -1.0
+14BUS-C0 1.41421356 60 120.0 -1.0
+14BUS-M0-1 1.020.00001 -1.0
+11BUS-M0-1 -.4 .019500
+14BUS-FS 0.002091 0.00001 -1.0
+19 UM { Beginning of U.M. data (Type-19 source)
+11
+BLANK card ending class-1 U.M. data
+ 1 2 1111BUS-M1 1 1786.98 { 1st card of U.M. machine table
+C 1 2 1111BUS-M1 1 1786.98 0.0 1.E-2
+C Note about preceding card: The one on comments, with speed tolerance EPSOM =
+C 1.E-2 really is preferable. However, it results
+C in a significantly different (20-30% ?) transient
+C than the 1st subcase. To ease the comparison,
+C we repeat the sloppy solution using default EPSOM.
+ 1.550 0 0.3 1.5 1.0
+ 1.490 0
+1.657962127 19.31 BUS-FSBUS-M0
+0.0 0.0 BUS-A1 1 { 1st card of coil table
+0.001096 0.150 BUS-B1 1
+0.001096 0.150 BUS-C1 1
+0.00074 0.101 BUS-F0 1
+0.0131 0.055 1
+0.0540 0.036 1
+BLANK card ending all U.M. data
+C --------------+------------------------------
+C From bus name | Names of all adjacent busses.
+C --------------+------------------------------
+C BUS-A0 |TERRA *BUS-A1*
+C BUS-B0 |TERRA *BUS-B1*
+C BUS-C0 |TERRA *BUS-C1*
+C BUS-A1 |BUS-A0*UM1TLA*
+BLANK card ending EMTP source cards
+C Total network loss P-loss by summing injections = 3.060462493760E+00
+C Total network loss P-loss by summing injections = 4.749309543189E+08
+C Total network loss P-loss by summing injections = 4.749309483781E+08
+C Total network loss P-loss by summing injections = 4.749309483781E+08
+C Step Time BUS-A1 BUS-B1 BUS-C1 BUS-M1 BUS-M0 BUS-A1
+C BUS-A0
+C
+C BUS-M0 UM-1 UM-1 UM-1 UM-1 UM-1
+C BUS-M1 TQGEN OMEGM THETAM IPA IPB
+C 0 0.0 1.56469025 -.30754481 -1.2571454 1.0 1.0 1.38601852
+C 1.00131382 1.0013138 1.0 .937861106 1.3860101 -.95878667
+C 1 .001 1.25258147 .317818099 -1.5703996 1.00000077 1.0 1.40129158
+C 1.00131344 .998244785 1.0 .937861106 1.40129158 -.50952832
+C 2 .002 .764711905 .89137497 -1.6560869 1.00000314 1.0 1.22174997
+C 1.00131148 .994893975 1.0 .937861106 1.22174997 .010186855
+ BUS-A1BUS-B1BUS-C1BUS-M1BUS-M0 { Request for selective node voltage output
+BLANK card ending the specification of output variables
+C 500 0.5 1.6149836 -.48296496 -1.1320186 1.00511758 1.00883159 .944795926
+C .552751698 .679538565 1.0051174 .638940337 .944795926 -.85191135
+C Maxima : 1.65785372 1.66075108 1.65580126 1.00797985 1.00883159 1.4158664
+C 1.00131382 1.00252272 1.00882158 .937861106 1.4158664 1.40560972
+C Times of max : .049 .038 .077 .444 0.5 .034
+C 0.0 .015 .433 .06 .034 .056
+C Minima : -1.6581898 -1.6603141 -1.6560869 .98886644 .990030962 -1.4042214
+C .29939589 .270787035 .987919779 .329902805 -1.4042214 -1.4126707
+C Times of min : .024 .013 .002 .158 .215 .059
+C .296 .344 .159 .356 .059 .031
+ PRINTER PLOT
+ 193 .1 0.0 1.0 BUS-M1BUS-M0 { Plot limits: (-1.001, 0.000)
+ 193 .1 0.0 1.0 UM-1 THETAM { Plot limits: (0.000, 9.379)
+BLANK card ending all plot cards
+BEGIN NEW DATA CASE
+BLANK
+
|