BEGIN NEW DATA CASE C BENCHMARK DCPR-7 C Test of 3-phase Pi-circuit that is excited by 3 in-phase sources that are C present during the phasor solution. No transients (phasor continuation). DIAGNOSTIC 0 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 PRINTED NUMBER WIDTH, 13, 2, { Request maximum precision (for 8 output columns) .05 1.0 60. 60. 1 1 1 1 1 -1 2 -1 { Turn off the diagnostic on step number 2 RECA .001 { Short the receiving end through R=1.E-3 RECB .001 { ohm resistors, so that lots of current RECC .001 { will flow (no subtle effects here!). 1SENDA RECA 1.0 1.0 1.E4 { 1st card of 3-phase Pi-circuit 2SENDB RECB 0.7 0.3 -2.E3 1.0 1.0 1.E4 3SENDC RECC 0.7 0.3 -2.E3 0.7 0.3 -2.E3 1.0 1.0 1.E4 BLANK card ending branch cards GENA SENDA -1.0 9.0 { 1st of 3 permanently-closed switches GENB SENDB -1.0 9.0 GENC SENDC -1.0 9.0 BLANK card ending switch cards 14GENA 100. 1.0 { Note all 3 sources} -1. 14GENB 100. 1.0 { have a phase angle} -1. 14GENC 100. 1.0 { of zero degrees.} -1. BLANK card ending source cards C Total network loss P-loss by summing injections = 6.246626371768E+03 C Output for steady-state phasor switch currents. C Node-K Node-M I-real I-imag I-magn C GENA SENDA 0.41644176E+02 -0.45752035E+00 0.41646689E+02 C GENB SENDB 0.41644176E+02 -0.45752035E+00 0.41646689E+02 C GENC SENDC 0.41644176E+02 -0.45752035E+00 0.41646689E+02 C Last inject: GENC C Last inject: SENDC 100. 100. 41.644175811789 41.646688990975 C Last inject: 0.0 0.0 -.4575203468966 -0.6294501 C Step Time RECC RECB RECA SENDC SENDB C C GENC C *** Phasor I(0) = 0.4164418E+02 Switch "GENA " to "SENDA " closed C *** Phasor I(0) = 0.4164418E+02 Switch "GENB " to "SENDB " closed C *** Phasor I(0) = 0.4164418E+02 Switch "GENC " to "SENDC " closed C 0 0.0 .0416441758 .0416441758 .0416441758 100. 100. C 100. C 1 .05 .0397499231 .0397499231 .0397499231 95.10565163 95.10565163 C 95.10565163 1 C 20 1.0 .0416440951 .0416440951 .0416440951 100. 100. C 100. C Variable max : .0416441758 .0416441758 .0416441758 100. 100. C 100. C Times of max : 0.0 0.0 0.0 0.0 0.0 C 0.0 C Variable min : -.041644069 -.041644069 -.041644069 -100. -100. C -100. C Times of min : 0.5 0.5 0.5 0.5 0.5 C 0.5 PRINTER PLOT { Axis limits : (-4.164, 4.164) 143 .1 0.0 1.0 RECA { This receiving end voltage is nice & sinusoidal BLANK card ending plot cards BEGIN NEW DATA CASE BLANK