BEGIN NEW DATA CASE C BENCHMARK DCPR-20 C Test of "JMARTI SETUP" from DCNEW-3, only with DIAGNOSTIC printout DIAGNOSTIC 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 9 JMARTI SETUP BRANCH JDA LMA JDB LMB JDC LMC LINE CONSTANTS 1.3636 .05215 4 1.602 -20.75 50. 50. { 1st conductor card 1.3636 .05215 4 1.602 -19.25 50. 50. { Etc. for remaining 2.3636 .05215 4 1.602 - 0.75 77.5 77.5 { conductors of 500 2.3636 .05215 4 1.602 0.75 77.5 77.5 { kV overhead line 3.3636 .05215 4 1.602 19.25 50. 50. { from "John Day" to 3.3636 .05215 4 1.602 20.75 50. 50. { "Lower Monumental" 0.5 2.61 4 0.386 -12.9 98.5 98.5 { (138 miles long). 0.5 2.61 4 0.386 12.9 98.5 98.5 BLANK card ending conductor cards of imbedded "LINE CONSTANTS" data case 100. 5000. 1 138. 1 3-2 100. 60.00 1 138. 1 3 100. .01 1 138. 1 9 10 3 BLANK card ending frequency cards of imbedded "LINE CONSTANTS" data case BLANK card ending imbedded "LINE CONSTANTS" data case 1 .30 30 0 1 1 0 0 .30 30 0 1 1 0 0 .0 BLANK card ending "JMARTI SETUP" data cases BEGIN NEW DATA CASE BLANK