KARD 1 2 3 4 5 6 10 11 12 13 14 15 KARG 1 3 5 2 4 6 7 9 11 8 10 12 KBEG 9 9 9 3 3 3 9 9 9 3 3 3 KEND 14 14 14 8 8 8 14 14 14 8 8 8 KTEX 1 1 1 1 1 1 1 1 1 1 1 1 C ----- CCT 1 -------------- IMPEDANCE MEASUREMENT ------------------------ C ** JUMPERS TO LINE MODEL SEGMENT FOR CURRENT INJECTION GENIA SEND_A .001 0 GENIB SEND_B .001 0 GENIC SEND_C .001 0 C C ** JUMPERS TO SHORT CIRCUIT OTHER END OF LINE MODEL SEGMENT RECV_A .001 0 RECV_B .001 0 RECV_C .001 0 C C ** SHUNT RESISTANCE TO LIMIT RESONANT IMPEDANCE TO 100K OHMS GENIA 100.E3 0 GENIB 100.E3 0 GENIC 100.E3 0 C C C ----- CCT 2 -------------- IMPEDANCE MEASUREMENT ------------------------ C ** JUMPERS TO LINE MODEL SEGMENT FOR CURRENT INJECTION GENID SEND_D .001 0 GENIE SEND_E .001 0 GENIF SEND_F .001 0 C C ** JUMPERS TO SHORT CIRCUIT OTHER END OF LINE MODEL SEGMENT RECV_D .001 0 RECV_E .001 0 RECV_F .001 0 C C ** SHUNT RESISTANCE TO LIMIT RESONANT IMPEDANCE TO 100K OHMS GENID 100.E3 0 GENIE 100.E3 0 GENIF 100.E3 0 C ------------------------------------------------------------------------- C BLANK CARD ENDING BRANCH CARDS ============================================ BLANK CARD ENDING SWITCH AND VALVE CARDS ================================== C C C ** CURRENT SOURCES FOR IMPEDANCE MEASUREMENT 14GENIA -1 1.00 60.0 0. -1.0 14GENIB -1 1.00 60.0 - 0. -1.0 14GENIC -1 1.00 60.0 0. -1.0 C 14GENID -1 1.00 60.0 0. -1.0 14GENIE -1 1.00 60.0 - 0. -1.0 14GENIF -1 1.00 60.0 0. -1.0 C C BLANK CARD ENDING SOURCES ================================================= C C ** OUTPUTS FOR IMPEDANCE TEST GENIA GENIB GENIC GENID GENIE GENIF C BLANK CARD ENDING NODE VOLTAGE OUTPUTS ====================================