/SOURCE 14WHITE 1.02 60. 0.0 -1. /BRANCH WHITE YELLOW .05 .20 YELLOWGREEN .05 .20 GREEN RED .05 .20 RED BLUE .10 .40 /LOAD FLOW C Next come power constraints of the load flow. There will be one C for each non-slack generator: RED -0.4 -.14 .85 1.15 GREEN 1.0 0.3 .85 1.15 BLUE -.15 .025 .85 1.15 YELLOW -0.6 -0.2 .85 1.15 C The following load-flow miscellaneous data card has two peculiarities. The C use of VSCALE = 1.414 is the special flag requesting RMS rather than peak C voltages. The use of KTAPER = 0 ensures constant acceleration factors C (this works for this data). C NNNOUT NITERA NFLOUT NPRINT RALCHK CFITEV CFITEA VSCALE KTAPER 1 500 20 1 .00001 0.1 7.0 1.414 0 /REQUEST FIX SOURCE { An EMTP load flow will satisfy requested phasor power injections.